HomeMy WebLinkAbout236466_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10194932 PROJECT ADDRESS: 2209 S Towner St PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/29/2017 INITIAL REVIEW 1/9/2018 EXPIRATION 5/28/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Marvin Barriga 3. TEL: (951)751-7813 FAX: VALUATION: $55,987.00 EMAIL: marvinbga@aol.com FLOOD ZONE: X-0602320259J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2016California Residential Code (CRC); 2016 California Building Code (CBC); CMC = 2016California Mechanical Code; CPC = 2016 California Plumbing Code; CEC = 2016 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Please refer to red marks on the drawings for both architectural and structural and T-24 drawings as additional plan check comments and revise drawings to show compliance. Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment, if needed. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (714-647-5804). Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (714-647-5840). - Public Works Agency approval (714-647-5039). - Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.Show minimum of 5’-0” setback for new addition and new garage.Provide dimensioned eave / overhang / projection setback to all property lines.Provide existing and proposed contours/spot elevations to indicate general site slope and drainage pattern.(CBC 107). Lots shall be graded to drain surface water away from foundation walls. The grade shall fall a minimum of 6 inches within the first 10 feet. (CRC R401.3)Show location of heating equipment on the plans. (CRC R303.8). For an FAU located in the attic provide a minimum access of 22 x 30 inches, a 24-inch wide walkway, a 30-inch deep work platform, and electric light outlet adjacent to the furnace and switched by the opening. (CMC 904.11 & 305)Interior spaces intended for human occupancy shall be provided with heating facilities capable of maintaining a room temperature of 68 degrees Fahrenheit at a point 3 feet above the floor and 2 feet from exterior walls in all habitable rooms. (CRC R303.8)Shower compartments and walls above bathtubs with shower heads installed shall be finished with a smooth, nonabsorbent surface to a height of not less than 72” above the floor. (CRC R307.2)Provide framing detail for 30”x30” attic access when CJ is at 16”O.C.Show location of attic access on architectural and roof framing plan, for each enclosed attic space with a maximum vertical height greater than 30 inches, provide a minimum of 22 x 30 inches attic access. (CRC R807.1) Specify that the maximum slope of any door landing shall not exceed ¼ inch per foot. (CRC R311.3) Fireblockingis required in concealed spaces 10’ o.c. horizontal, vertically at the ceiling and floor levels, connections between horizontal and vertical spaces, concealed spaces between stair and landing, openings around vents, pipes, ducts, cables, wires, chimneys and fireplaces. (CRC R302.11)Show panel layout pattern for new floor and roof diaphragm. For plywood floor and roof diaphragm specify thickness, grade, T&G edges, panel span rating, nailing schedule and panel layout pattern. (CBC 2305, T2305.2.3, 2306.3, T2306.3.1, and T2306.3.2)Show location of new ridge board and positive attachment for existing and new ridge on the drawings. The City has encountered a large number of inspection problems arising from a lack of specific framing details. The following listed items are required to be shown on the plans (CBC 107.1): - All plumbing walls are to be framed with a minimum of 6" studs. - Double walls used as plumbing walls are to be a minimum of 8" wide and no "flat" studs permitted. Staggered studs are acceptable. - Permissible notching and boring of joists are to be shown on the plans and shall not exceed CBC Section 2308.10.4.2 allowances. - Notching of exterior and bearing/nonbearing walls shall not exceed 25%/40% respectively. Bored holes in bearing/nonbearing walls shall not exceed 40%/60% respectively. In no case shall the edge of the bored hole be nearer than 5/8 inch to the edge of the stud. (2308.9.10 and 2308.9.11) - Header and trimmer details for doors and windows are to be shown with full length trimmers, specifying the size of the header and trimmer. (2308.10.4.3) - All stud bearing walls are required to comply with the minimum requirements for load bearing walls. Show location(s) and provide typical construction details. (2308.9)The residence shall conform to the State Energy Conservation Standards and show compliance with followings: - Please check with designer for slab on grade or raised floor and revised calculations if needed. - Signed Energy Efficiency Documents must be printed on the plans. Documentation author and designer cannot be the same person. - The energy plan check consultant must also complete the attached “Energy Conservation Plan Check Consultant Qualification Statement”. Please see attached. Please complete provided Forms on the drawings (SB 407 and CalGreen).