HomeMy WebLinkAbout237595_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10195294 PROJECT ADDRESS: 1002 W Washington Ave PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 1/11/2018 INITIAL REVIEW 2/8/2018 EXPIRATION 7/10/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Camilo Gomez 3. TEL: (626)688-9149 FAX: VALUATION: $320,000.00 EMAIL: cgomez@tektonteam.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2010 California Residential Code (CRC); 2010 California Building Code (CBC); CMC = 2010 California Mechanical Code; CPC = 2010 California Plumbing Code; CEC = 2010 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). -Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). -Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. -Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). In addition to other fees, a "Park Acquisition and Development Fee" in the amount shownbelow shall be required pursuant to a resolution of the City Council for the Recreation andCommunity Services Agency; net addition of ________ bedroom(s).Amount of $6,832.81; net addition of 5 bedroomsAmount of $6,141.46; net addition of 4 bedroomsAmount of $5,546.44; net addition of 3 bedroomsAmount of $4,133.98; net addition of 2 bedroomsAmount of $3,102.61; net addition of 1 bedroom New one- and two-family dwellings and townhouses shall have an automatic fire sprinkler system installed in accordance with CRC Section R313.3 or NFPA 13D. Contact the Santa Ana Fire Department for fire sprinkler permit requirements (714) 647-5839. (CRC R313) Provide and show on the plans, house street number visible and legible from street. (Minimum 4”High x 1” Wide) CRC R319 Provide existing and proposed contours/spot elevations to indicate general site slope and drainage pattern. (CBC 107) Lots shall be graded to drain surface water away from foundation walls. The grade shall fall a minimum of 6 inches within the first 10 feet. (CRC R401.3) Provide dimensions for attic access. Provide a roof plan, show all ridges, hips and valleys. Provide or call out a platform in front of the mechanical unit in the attic. Show on plan that the unit is solar ready per the Green building code. In addition, show the location of the EV raceway to make Provide a construction section through the building. Provide energy calcs, and make sure the conformance forms on plans and calcs are signed by the designer. Provide structural design calculations to show adequacy of the 1” anchors embedded in concrete as shown on plans are adequate to resist applied loads.