HomeMy WebLinkAbout237595_4_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10195294
PROJECT ADDRESS:
1002 W Washington Ave
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/11/2018
INITIAL REVIEW
2/8/2018
EXPIRATION
7/10/2018
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Camilo Gomez
3.
TEL:
(626)688-9149
FAX:
VALUATION: $320,000.00
EMAIL:
cgomez@tektonteam.com
FLOOD ZONE: X-0602320144J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2010 California Residential Code (CRC); 2010 California Building Code (CBC); CMC = 2010 California Mechanical Code; CPC = 2010 California Plumbing Code; CEC = 2010 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
-Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
-Grading Permit. Application is made through the Building Safety Division (647-5800) and the
plan review is by the Public Works Agency (647-5039).
In addition to other fees, a "Park Acquisition and Development Fee" in the amount shownbelow
shall be required pursuant to a resolution of the City Council for the Recreation andCommunity
Services Agency; net addition of ________ bedroom(s).Amount of $6,832.81; net addition of 5 bedroomsAmount of $6,141.46; net addition of 4 bedroomsAmount of $5,546.44; net addition of 3 bedroomsAmount of $4,133.98; net addition of 2 bedroomsAmount of $3,102.61; net addition of 1 bedroom
Show on plan that the unit is solar ready per the Green building code. In addition, show the location of the EV raceway to make .
Provide structural design calculations to show adequacy of the 1” anchors embedded in concrete as shown on plans are adequate to resist applied loads.
Energy sheets on the plan should be signed by the person prepared the energy report.
The reference to sheet S1.3 on the garage plans in incorrect. There is no sheet S1.3/.
Provide shear reinforcement for the footing supporting the 12” Simpson at the front of the garage. ( the garage footing at the front of the garage should be designed as a grade beam.