HomeMy WebLinkAbout240457_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196122 PROJECT ADDRESS: 1801 E Carnegie Ave PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 4/13/2018 INITIAL REVIEW 4/27/2018 EXPIRATION 10/10/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Reuben Walters 3. TEL: (949)650-9992 FAX: VALUATION:$432,810.00 EMAIL: FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Public Works Agency approval (647-5039) - County of Orange Health Department approval on the corrected/final set of drawings ((714)433-6000) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceOn the wall section, show: - Size, spacing, and material of framing members, in addition to the height of the walls. - Note gauge and ICC Research Report number and installation/construction requirements for metal framing members.The accessible bathrooms need to be in the same vicinity as the other bathrooms. The bathrooms serving the lab are not accessible. You can, move the corridor such that both restrooms are in the same area.Justify the allowable area of the building based on the mixed use equation.Specify if the building is an S1 or S2 occupancy.What is the BULL PEN use shown on the floor plan.On the detail of wall 1 there is a reference to structural plans. Please reference the sheet and detail.Details are showing walls with cross bracing on the top. Where such a detail does apply.Provide details and notes for the accessible bathrooms including signage. Please ensure that the signage on the door and next to the door complies with the chapter 11B.