Loading...
HomeMy WebLinkAbout242343_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196661 PROJECT ADDRESS: 6 E Hutton Center Dr PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: I A, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/6/2018 INITIAL REVIEW 6/6/2018 EXPIRATION 12/3/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Gary Williams 3. TEL: (949)701-4030 FAX: VALUATION:$5,000.00 EMAIL: gwilliams@lpainc.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. (FYI) This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceIndicate ICC approval for reused ceiling system located in the corridor area. Please note on the drawings the fire rating of existing suspend ceiling. Clarify if corridor area where modified is one hour fire rated and note on the drawings. Provide corridor detail to show wall and ceiling fire rating including fire dampers location (wall or ceiling mounted). In-lieu of providing structural calculations and drawings for suspended ceiling indicate ICC approval number for suspended ceiling. Clarify Note “M” on Sheet TA7.1, for location of tissue dispenser and sanitary napkin show required clearance on the drawings. Please note that area above grab bar to be unobstructed at 12” minimum and 1.5” at bottom and clarify if detail #4 is applicable as part of proposed revision. Section 11B-609.