Loading...
HomeMy WebLinkAbout242462_1_Corrections.docxSPC PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196697 PROJECT ADDRESS: 1951 E Dyer Rd PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: III A, SPK OCCUPANCY CLASSIFICATION(S): R-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/11/2018 INITIAL REVIEW 7/31/2018 EXPIRATION 12/8/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Brandon Bertoglio 3. TEL: (714)271-9370 FAX: VALUATION: EMAIL: bbertoglio@allresco.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.The cumulative loads on the anchor bolts, both tension and compression, are high in certain areas. There is a note on the holdown plans indicating that the design of the anchor bolt connection to the structure is to be done by the engineer of record. Please provide design calcs and make sure the holdown plans, reference the details provided on the original set of plans, for such connection.