Loading...
HomeMy WebLinkAbout241283_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196355 PROJECT ADDRESS: 3330 S Harbor Blvd PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/7/2018 INITIAL REVIEW 5/16/2018 EXPIRATION 11/3/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Debra Pember 3. TEL: (714)334-8385 FAX: (949)265-6959 VALUATION:$50,000.00 EMAIL: debra@developersedge.com FLOOD ZONE:X-0602320258JINSTRUCTIONS: Numbersinbracketsrefertocodesectionsof 2016CaliforniaBuilding Code[CBC],2016CaliforniaPlumbingCode[CPC],2016CaliforniaMechanicalCode[CMC],2016California ElectricalCode[CEC],2016CaliforniaEnergyCode(2016BuildingEnergyEfficiencyStandards[BEES]),and2016 CaliforniaGreenBuildingsStandardsCode[CalGreen] Correctoriginaldrawings.Reprintandsubmit3newsetstogetherwiththe“marked-up”set.Returnthiscorrections list with corrected plans. In the Item number column, ☒ in the checkbox represents correction requested. IntheRespondcolumn,pleaseindicatethesheetnumberanddetailornote numberontheplanwherethe corrections are made. Itemize anychanges,revisions,oradditions madeto drawingsthatarenotadirectanswertoa correctionona separate sheet. Additionalplancheckfeewill be requiredafterthirdreviewonhourlyrate basis. ADDITIONALCORRECTIONS: Item # Sheet # Corrections Requested Respond ☒ A1.2, A2.2 Sheet A0.3, A1.2 and Sheet A2.2 shows a “Mezzanine” floor plan. It appears the intended design on the second floor tenant improvement as a second floor story and not a Mezzanine as defined in the building code and Mezzanine Section 505. Please clarify design intent as either a second floor story or Mezzanine per building code Section 505. Revise title on drawings as necessary. ☒ A0.1 Construction of fire rated Exit passageway shall be continuous through the proposed canopy area. ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐