Loading...
HomeMy WebLinkAbout242949_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196839 PROJECT ADDRESS: 1030 S Newhope St PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/22/2018 INITIAL REVIEW 7/2/2018 EXPIRATION 12/19/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Terry Booth 3. TEL: (714)981-5729 FAX: VALUATION:$43,404.00 EMAIL: Terry@newlandconstruction.com FLOOD ZONE:X-0602320256JAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Residential Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review. All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered engineer. Provide a clear Roof Framing plan for this proposed addition with clear construction details.Submitted sheet S-2 is missing framing details and needs to be updated. The proposed lateral loads resisting design shown on sheet S-1 seems to be weak. Provide structural calculation to support the design or provide additional shear walls as marked on this sheet to reinforce the structure. Provide fans for the existing and proposed the bathrooms to comply with CBC Section R303.3.1. (Fans to have a humidity control) The “Seal door” from the garage to the existing kitchen shall be replaced with a wall to comply with the garage wall requirement of CBC Section 302.6 The proposed doors “D02” & “D07” from the garage to the house shall have 20 minutes rating per CBC Section R302.5.1. please update the door schedule to reflect this.All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a). This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). -Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. Show location of minimum 20x30-inch attic access with 30-inch minimum headroom in accordance with CBC1209. Also, MC305.0 requires that appliances shall be accessible for inspection, service, repair, and replacement without removing permanent construction. MC904.11 requires that an attic, in which an appliance is installed, shall be accessible through an opening at least as large as the largest component of the appliance and not less than 22 inches x 30 inches. In lieu of openable windows (skylights) for habitable rooms a mechanical ventilating system, complying with the Mechanical Code, shall be provided. Show size of unit and location of registers for any room that does not comply with minimum exterior opening for natural light and or ventilation. Wall covering shall be cement plaster, tile or approved equal to 72 inches above drain at showers or tub with showers. Materials other than structural elements shall be moisture resistant. In every sleeping room below the fourth story and in the basements of dwelling units, at least one openable emergency escape and rescue window or door shall open directly into a public street, pubic alley, yard or exit court, meeting all of the following: -An openable area of not less than 5.7 square feet (5.0 square feet for ground-floor openings); -A minimum 24 inch clear openable height; -A minimum clear openable width of 20 inches; -A sill height not over 44 inches above the floor. -show compliance for the interior bedroom. This bed room does not have an emergency escape window; therefore it cannot be a bed room. Either the family room is built without a permit or the kitchen has been extended without a permit to cause this situation. Revise the drawing to show compliance with CRC Section R310 for this bedroom.Show the location(s) of hard-wired smoke alarm(s) with a battery back up in each sleeping room and at a point centrally located in the corridor or area giving access to each sleeping area. (Battery-operated smoke detectors are permitted in existing construction only.Show location(s) of Carbon Monoxide alarm(s) for this project. The City has encountered a large number of inspection problems arising from a lack of specific framing details. The following listed items are required to be shown on the plans: -All plumbing walls are to be framed with a minimum of 6" studs. -Permissible notching and boring of joists are to be shown on the plans and shall not exceed CRC allowances. -Notching of exterior and bearing/nonbearing walls shall not exceed 25%/40% respectively. Bored holes in bearing/nonbearing walls shall not exceed 40%/60% respectively. In no case shall the edge of the bored hole be nearer than 5/8 inch to the edge of the stud. Show how dwelling is provided with comfort heating facilities capable of maintaining a room temperature of 68oF at a point of 3 feet above the floor in all habitable rooms. The residence shall conform to the State Energy Conservation Standards. Submit forms and calculations for review and blueprint the final forms on the plans. -Signed Energy Efficiency Documents must be printed on the plans. -Also, submit 2 copies of signed Energy Efficiency calculations. -The permit applicant shall be responsible for obtaining an energy plan check from a consultant who is qualified to perform an energy efficiency analysis in accordance with the California Code of Regulations (CCR), Title 24, Part 1 (Administration) and Part 6 (2016 California Energy Code). The plan check consultant must sign documentation certifying that a thorough, competent review has been performed on behalf of the Enforcement Agency. -The corrected/final drawings shall have the required energy efficiency compliance documentation with completed signature blocks filed on the plans. -The energy plan check consultant must sign documentation forms on behalf of the Building Safety Division. -The energy plan check consultant must also complete the attached “Energy Conservation Plan Check Consultant Qualification Statement”. -Refer to the attached public handouts titled “Energy Efficiency Compliance” and “Energy Efficiency Compliance Documentation”. The Title 24 that was submitted has the wrong climate zone for City of Santa Ana. please change the climate zone from zone 6 to zone 8, and submit it for recheck. Provide designed ridge beams (4 x min.) for open beam vaulted ceilings when ceiling joists or rafter ties are not provided. Ridge/hip/valley members shall be designed as vertical load carrying members when roof slope is less than 3:12. Provide calculations. Provide structural calculations and drawings prepared by a California Licensed Architect or Registered Civil Engineer for all structural work to be performed under the subject building permit application including:The proposed structural design is inadequate to resist lateral forces/uplift wind pressure. Show roof/floor diaphragm nailing, wall bracing, shear connections, tie-down hardware and hold-down anchors. Submit lateral design. See other red marks on the plan. Please resubmit the marked up set with revised drawings for recheck.