HomeMy WebLinkAbout239784_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10195932 PROJECT ADDRESS: 2941 N Hesperian Way Unit# B PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 3/26/2018 Fire damaged building and Ti Acc INITIAL REVIEW 4/9/2018 EXPIRATION 9/22/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Ben Phan 3. TEL: (714)251-4537 FAX: VALUATION:$250,000.00 EMAIL: Benphanconsultant@gmail.com FLOOD ZONE:X-0602320144J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans. Please refer to mark up set of drawings for additional plan check comments. Return marked up set of drawings with corrected sets. (when needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information. Please remove EMP Sheets from drawings.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceSubmit a letter by a California licensed engineer or architect to evaluate the fire damage to roof, connections as well as bearing walls. Provide a copy on each set of drawings.Occupancies storing, handling, using, and/or selling hazardous materials, liquids, and chemicals shall submit a list of all said materials, listing their quantities and how they relate to specific California Building Code Table items. If applicable note on the Floor Plan, type and quantity of hazardous material in each control area and fire-resistive rating for fire barriers. Occupancies using hazardous materials are subject to special requirements. It is the applicant’s/owner’s responsibility, PRIOR TO SUBMITTAL, to make this known to the Building, Planning, and Fire Departments.When applicable, Submit structural engineering calculations for new wall construction with height greater than 14’. Provide connection detail for top and bottom connection of wall.Please indicate occupancy for each room area in compliance with Section 303 such as B, S or F occupancy and provide occupancy separation as required by Table 508.4, 2016 CBC.Show/note ventilation requirements on the plans in accordance with the 2016 CBC and California Mechanical Code (CMC) requirements for each type of use. Note on drawings: Provide mechanical ventilation for each area/room in accordance with the 2016 California Mechanical Code.Note on drawings: Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of useIndicate ICC approval number for new skylights and provide detail of attachment to roof. Also provide detail for equipment attachment to roof including platform detail. Indicate ICC approval for sealant when roof in penetrated for attachment of equipment.Valuation of proposed project is calculated as $250,000.00. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access as noted in CBC Chapter 11-B, Division 2. Please refer to attached accessibility form and return completed Form to Building department.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC 11-B, Division 2. - An accessible entrance - An accessible route to the altered area - Accessible restrooms (. - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarms (Parking to be as close as possible to entrance of building.Provide dimensioned floor layout of toilet room and shower room in compliance with Section 11B- 606, 11B-604, 11B-606 and 11B-608 of 2016 CBC.Toilet room and shower room as shown on the drawings do not provide sufficient information for code compliance reviewWhen existing toilet rooms are modified, Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.Note on the drawings hot water and drain pipes under lavatory shall be insulated.It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. Please remove notes referring to ADA or ANSI compliance. This project is reviewed for compliance with 2016 CBC.When a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section11B- 705, 2016 CBC. The truncated dome is to be around door landing at 36” width. Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 705.Provide parking data on the site plan showing the total number of parking spaces required by planning department and shown on the site plan. Provided the number of disabled accessible spaces and the number of van accessible spaces, showing compliance with CBC Table 11B-208.2. (Parking to be as close as possible to entrance of building.Showing compliance with CBC Division 5, andwith CBC Table 11B-208.2. Including the followings: Revise the drawings to show the words NO PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. In each parking area, a bumper or curb shall be provided and located to prevent encroachment of cars over the required width of walkways (account for front of car overhang).Provide parking space identification in accordance with CBC Division 5, including: - Each parking space reserved for persons with physical disabilities shall be identified by a reflecting sign permanently posted immediately adjacent to and visible from each stall or space, consisting of a profile view of a wheelchair with occupant in white on dark blue background. The sign shall not be smaller than 70 square inches in area and, when in path of travel, shall be posted at a minimum height of 80” from the bottom of the sign to the parking space finished grade and shall be un-obscured by a parked vehicle. Signs may also be centered on the wall at the interior end of the parking space. An additional sign or additional language below the symbol of accessibility shall state “Minimum Fine $250.” Spaces. An additional sign stating “Van Accessible” mounted below the symbol of accessibility. - An additional sign shall also be posted in a conspicuous place at each entrance to off-street parking facilities, or immediately adjacent to and visible from each stall or space. The sign shall not be less than 17” by 22” in size with lettering not less than 1” in height, with clearly and conspicuously states the following:Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or license plates issued for persons with disabilities may be towed away at owner’s expense. Towed vehicles may be reclaimed by telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a. - Provide assurance on the drawings that existing signage language reflects the paragraph above.Provide drawings to show compliance with following items;All doors require a level floor landing on each side Provide typical door threshold details (1/2” max threshold) and when applicable provide details of change in floor covering materialThe width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.Hand-activated door opening hardware shall be centered between 34” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction. Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc) to comply with disabled access requirements. Revise door schedule to include accessibility compliance. All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Tactile exit signs shall be required at the following locations: (identify location of each applicable signage on the floor plan or reflected ceiling plan. - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” Visual exit sign shall be identified by a tactile exit sign with the words “EXIT ROUTE.”Clarify path of accessible on the drawings and indicate slope (5% max) and cross slop (2% max.) on the drawings. At every entrance and at every major junction along or leading to an accessible route of travel, there shall be a sign displaying the international symbol of accessibility. Signs shall indicate the direction with ISA sign to accessible building entrances and facilities. Show location of path of travel including slope and cross slop on the drawings.Provide structural calculations and drawings, stamped and signed by a California licensed architect or registered civil engineer for: - New mechanical equipment on roof (note on Roof Framing Plan weight of each existing and new piece of equipment on the roof) - New equipment screening including detail/s on the drawings. Roof screen is required by planning department.