HomeMy WebLinkAbout243205_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10196919
PROJECT ADDRESS:
1125 S Lowell St
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
7/3/2018
INITIAL REVIEW
10/11/2018
EXPIRATION
12/30/2018
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Ruben Pena
3.
TEL:
(714)552-5731
FAX:
VALUATION: $59,982.00
EMAIL:
rpena@inkminded.com
FLOOD ZONE: X-0602320257J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2016 California Residential Code (CRC); 2016 California Building Code (CBC); CMC = 2016 California Mechanical Code; CPC = 2016 California Plumbing Code; CEC = 2016California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
Dimension the width of the landing and stairs outside the proposed dining area.
Show all kitchen counters on floor plans.
Dimension the height of the deck outside the dining area.
Cross-reference the proposed stairs with a section that shows the run and rise of the steps.
The garage is too close to the proposed addition. Provide 5/8” drywall on the garage side of the wall facing the residence.
Provide lateral support for the patio cover
Reference the details properly, example detail 4 on 7?
Clarify how the MST strap will bend to connect to the ridge or post.
Dimension the width of the footings.