HomeMy WebLinkAbout242488_3_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196708 PROJECT ADDRESS: 2927 W Willits St PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/11/2018 INITIAL REVIEW 6/27/2018 EXPIRATION 12/8/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Joel Soto 3. TEL: (714)654-2658 FAX: VALUATION: $80,000.00 EMAIL: FLOOD ZONE: X-0602320256J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2016 California Residential Code (CRC); 2016 California Building Code (CBC); CMC = 2016California Mechanical Code; CPC = 2016 California Plumbing Code; CEC = 2016 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. Provide a dimension of the stair’s width. On the foundation plan, provide a different shade for the new footing proposed. Holdown anchors using epoxy must have special inspection, provide notations on the details and plans. Structural calcs page 7, specify those anchors using epoxy, and provide structural calcs and bolt specs( length diameter etc.) to show adequacy.( these are for the bolts supporting the holdown anchors specifically the large ones HDU’s. Per section 4.1.3 of ESR 2330, the holdown anchors are to be separately designed to resist the uplift loads. Please provide structural calcs and specifications as called out in correction 10 above.