HomeMy WebLinkAbout241514_3_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10196418
PROJECT ADDRESS:
1809 N Nancy Ln
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3.1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/14/2018
INITIAL REVIEW
5/28/2018
EXPIRATION
11/10/2018
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Allon Shelly
3.
TEL:
(310)570-0077
FAX:
VALUATION: $15,000.00
EMAIL:
allonshelly@gmail.com
FLOOD ZONE: X-0602320143J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2016 California Residential Code (CRC); 2016 California Building Code (CBC); CMC = 2016 California Mechanical Code; CPC = 2016 California Plumbing Code; CEC = 2016 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a).
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
-Public Works Agency approval (647-5039).
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper.
Provide building information on plans:
- Occupancy type: R3.1
- Construction type: Type V – B
- Fire sprinklered: Yes (will be provided)
Provide automatic sprinkler system. R335.5.1.
Provide smoke alarm R335.5.2.
Provide audible alarm signal section R 335.2.1
Please provide visible alarms section R335.5.2.3.
Please make a note on the drawings “ Every Licensee admitting or retaining a bedridden resident shall, within 48 hours of resident’s admission or retention in the facility, notify the local fire authority with jurisdiction of the estimated length of time the resident will retain his or her bedridden status in the facility.” CRC R335.3.1
Show window in patient room #4, is in compliance with emergency egress.
Ramps serving the egress door shall have a slope of not more than 1:12 . R311.8.1.
Show size of the landing at door #150.
Handrails shall be provided not less than one side of ramps. R311.8.3.
Provide detail to show handrails are in compliance with R311.8.3.
Show interior wall and ceiling finish is in compliance with R335.4.1and show on the drawings per table 803.11
Group R-3.1 occupancy shall have minimum of 2 exits. R335.6.2.
A means of egress shall not pass through more than one intervening room. R335.6.3.4.
Non Ambulatory clients shall have access to at least one of the required exits per R335.6.3.2. (Number 1)
Please clarify and show use of the calculation on the drawings.
Engineer of record shall provide details and stamp the drawings.