HomeMy WebLinkAbout242647_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10196738 PROJECT ADDRESS: 2008 W Fifth St Unit# A PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: II B OCCUPANCY CLASSIFICATION(S): A-3, B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/21/2018 INITIAL REVIEW 8/28/2018 EXPIRATION 12/18/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Mark Peterson 3. TEL: (213)236-2553 FAX: VALUATION:$1.00 EMAIL: mark.peterson@stvinc.com FLOOD ZONE:X-0602320257J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS GENERAL REQUIREMENTSThe drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Building Standards Code with local amendments.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.All persons preparing plans and specificationsshall sign those plans and specifications. This requirement applies to both exempt and non-exempt projects. Business and Professions Code Chapter 3, Division 3, Section 5536.1(a).Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:☒Planning Division approval on the corrected/final set of drawings (647-5804)☒Public Works Agency approval (647-5039)☒Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700)☒Police Department approval on the corrected/final set of drawings (647-5840)☒School District Compliance Certificate; a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout.☐County of Orange Health Department approval on the corrected/final set of drawings (667- 3600)☒Grading Permit - Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039)☒Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceA separate Building Permit Application is required for: Each building, Each structure, Each sign, Trash enclosure(s), Fence(s), Block wall(s), Light standard(s), Pedestrian protection, Demolition, Site improvements, Storage Racks, Screen Wall for Proposed Equipment.State Division of Occupational Safety Permit (Cal/OSHA) (939-0145). A Cal/OSHA permit is required: For construction of trenches or excavations which are 5‘or deeper and into which a person is required to descend. The construction or demolition of any building, structure, false-work, or scaffolding more than three stories high or the equivalent height.Delete all notes and details from drawings that are not a part of the work to be done under the subject building permit application. Clearly indicate the scope of work on the building permit application.Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application.Construction drawings must clearly show all work to be done under the subject building permit application. Site Plan Review – Sheet Z-PG02Specify Fire Separation Distance from the face of East exterior-wall on the maintenance building to the property line. Fire separation distance is required to determine the fire rating of exterior wall and its openings.Specify Fire Separation Distance from the face of South exterior-wall on the maintenance building to the property line. Fire separation distance is required to determine the fire rating of exterior wall and its openings.Specify Fire Separation Distance from the face of South exterior-wall on the maintenance building to the assumed property line. Assumed property line shall be located between the maintenance building and the car-wash building. The concept of assumed property line is use for relative fire exposure when one building catches on fire, how likely the fire spreads to the next building. The further the distance is between buildings, the less exposure.Specify Fire Separation Distance from the face of West exterior-wall on the maintenance building to the property line. Fire separation distance is required to determine the fire rating of exterior wall and its openings.Site plan shows two interior lot-line within the project site. Will there be a lot-line adjustment? If this is the case, provide exhibit recorded by the county for reference. The car-wash building is located on the property line. All buildings must be located within the property boundary line.Site plan indicates proposed sound wall #3 near fourth street. Separate permit shall be submitted to Planning and Building department for review.Site plan identifies the location of accessible parking spaces but there are no detailed specifications found in the plan. See page 6 and 7 for a list of required accessible parking requirements. Sheet Z-PG03Revise the referenced numbers under Building construction note #2a. The correct table numbers are 504.3 & 504.4.Revise the allowable area equation in Table “MF Building Type B”. Use the 2016 California Building Code (CBC) Equation 5-3 “Aa = At + (NS X If)”. The equation on the table was based on the 2013 edition of CBC.In Table “MF Building Type IIB”, verify the floor area on F-1 occupancy. The table shows 25,710 square foot; The area diagram shows 25,760 square foot.In Table “MF Building Type IIB”, the sub-total area does not add up. 5,800 + 25,710 + 2960 = 34,470. The plan shows a sub-total of 35,996 square foot.In Table “MF Building Type IIB”, provide an allowable area analysis for the second floor and the entire building according to Section 506.2.4.In Table “CW Building Type IIB”, Use the 2016 California Building Code (CBC) Equation 5-3 “Aa = At + (NS X If)”. The equation on the table was based on the 2013 edition of CBC.In Table “CW Building Type IIB”, the allowable area should be 92,000 square foot.In Table “CW Building Type IIB”, the designed area is 3,400 square foot. However, the diagram shows 4,775 square foot. Sheet Z-PG04Egress analysis have been reviewed. In general, number of provided exits, travel distances, common path of travel distances, egress widths and dead-end conditions meet building code requirement. There is one occupant number that needs to be verified. This area is located in the lobby. Egress calculations show exit door #101A can accommodate 440 occupants, and the actual occupant load number is 383. It is unclear how this number was calculated. The majority of the occupant load comes from the second floor large-conference room. Occupant load was calculated on the table but the aggregate sum of occupant load should be accounted for when egress path emerges from different spaces on the second floor. Provide calculations of total occupant load from the second floor to exitstairway #1. This number should be checked against the provided width for door #101A. Sheet Z-PG17Revise the minimum dimension from edge of wall to center-line of water closet to 17 inches on men’s accessible water closet and women’s accessible water closet.The water closet shall be positioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 17 inches minimum to 18 inches maximum from the side wall or partition, except that the water closet shall be 17 inches minimum and 19 inches maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in Section 11B-604.8.2 Ambulatory Accessible Compartments. Water closets shall be arranged for a left-hand or right-hand approach. §11B-604.2Revise the minimum dimension from the ground to the tissue dispenser to 19 inches on men’s accessible water closet and women’s accessible water closet.Toilet paper dispensers shall comply with Section 11B-309.4 Operation and shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be below the grab bar, 19 inches minimum above the finish floor and shall not be located behind the grab bars. Dispensers shall not be of a type that control delivery or that does not allow continuous paper flow. §11B-604.7 On the accessible-shower elevation drawing, provide dimension to show grab bars installed in a horizontal position, 33 inches minimum and 36 inches maximum above the finished floor measured to the top of gripping surface. Dimensional range implies construction tolerance beyond specified limits is not permitted.§11B-609.4 Sheet Z-PN12 Two-hour fire rated wall is specified in the electrical room. Door # 148B shall have a fire rating of minimum 90 minutes. Specify the minimum fire door rating on door schedule on sheet Z-PD40. Sheet Z-PN13 One-hour fire rated wall is specified in exit stairway #2. Door # 142A and #142B shall have a fire rating of minimum 45 minutes. Specify the minimum fire door rating on door schedule on sheet Z-PD40. Sheet Z-PN14 One-hour fire rated wall is specified in exit stairway #4. Door # 149A and #149B shall have a fire rating of minimum 45 minutes. Specify the minimum fire door rating on door schedule on sheet Z-PD40. Sheet Z-PN16One-hour fire rated ceiling is specified near the elevator. Provide one-hour fire rated ceiling assembly detail. Sheet Z-PN51Show accessible floor-space of 30 inches by 48 inches in front of a locker which is accessible. South Elevation drawing shows a bench in front of the lockers. Show dimensions on the bench and demonstrate reach range per section 11B-308.3 is adequate at the locker required to be accessible. PARKING SPACES Item # Sheet # Corrections Requested Respond ☐ Where parking spaces are provided, accessible parking spaces shall be provided in number and kind required per Section 11B-208 Parking Spaces. §11B-208.1 ☐ Provide ( ) accessible parking spaces as required byTable 11B-208.2. §11B-208.2 (See exceptions) ☐ Provide accessible spaces for each parking facility (parking lots and parking structures). The number of parking spaces required to be accessible is to be calculated separately for each parking facility; the required number is not based on the total number of parking spaces provided in all of the parking facilities provided on site. §11B-208 ☐ Ten percent of patient and visitor parking spaces provided to serve hospital outpatient facilities, and free- standing buildings providing outpatient clinical services of a hospital, shall comply with Section 11B-502Parking Spaces. §11B-208.2.1 ☐ Twenty percent of patient and visitor parking spaces provided to serve rehabilitation facilities specializing in treating conditions that affect mobility and outpatient physical therapy facilities shall comply with Section11B-502 Parking Spaces. §11B-208.2.2 ☐ One in every six or fraction of six parking spaces required by Section 11B-208.2 Minimum Number, but not less than one, shall be served by an access aisle 96 inches wide minimum placed on the side opposite the driver’s side when the vehicle is going forward into the parking space and shall be designated “vanaccessible”. All such spaces may be grouped on one Level of a parking structure. §11B-208.2.4, 11B-502, Fig 11B-502, 11B-502.3, & 11B-502.3.3 ☐ Accessible parking spaces complying with Section 11B- 502 Parking Spaces serving a particular building or facility shall be located on the shortest accessible routeof travel from adjacent parking to an accessible Entrance (as near as practical to an accessible entrance). §11B-208.3.1 ☐ In buildings with multiple accessible entrances with adjacent parking, accessible parking spaces complying with Section 11B-502 Parking Spaces shall be dispersed and located closest to the accessible entrances. §11B-208.3.1 ☐ In parking facilities that do not serve a particular building or facility, accessible parking spaces complyingwith Section 11B-502 Parking Spaces shall be located on the shortest accessible route of travel to an accessible pedestrian entrance of the parking facility.§11B-208.3.1 ☐ Dimension minimum 18-foot long car and van accessible parking space(s) and access aisle(s). §11B-502.2, Figures 11B-502.2 and 11B-502.3 ☐ Dimension minimum 9-foot width at accessible car parking space. §11B-502.2, Fig. 11B-502.2 & Fig.11B-502.3 ☐ Dimension minimum 12-foot wide accessible van parking space with minimum 5-foot wide access aisle. Van parking spaces shall be permitted to be minimum 9 feet wide where access aisle is 8-foot wide minimum.§11B-502.2, Figures 11B-502.2 and 11B-502.3 ☐ Car and van stall access aisle shall be 5 foot wide minimum and shall adjoin an accessible route. Two parking spaces shall be permitted to share a common access aisle. §11B-502.3, Figures 11B-502.2 and11B-502.3 ☐ Access aisles shall be marked with a blue painted borderline around their perimeter. The area within the blue borderlines shall be marked with hatched lines a maximum of 36 inches on center in a color contrasting with that of the aisle surface, preferably blue or white. The words "NO PARKING" shall be painted on the surface within each access aisle in white letters a minimum of 12 inches in height and located to be visible from the adjacent vehicular way. Access aisle markings may extend beyond the minimum required length. §11B-502.3.3, Figure 11B-502.3.3 ☐ Access aisles shall not overlap the vehicular way.Access aisles shall be permitted to be placed on either side of the parking space except for van parking spaces which shall have access aisles located on the passenger side of the parking spaces. §11B-502.3.4 ☐ Clearly show minimum vertical clearance of 8 feet 2 inches at accessible parking spaces and along at least one vehicle access route to such spaces from site entrances and exits. §11B-502.5 ☐ Parking space identification signs shall include the International Symbol of Accessibility complying with Section11B-703.7.2.1 International Symbol of Accessibility. §11B-502.6, Figure 11B-703.7.2.1 ☐ Signs identifying van parking spaces shall contain additional language or an additional sign with the designation “van accessible.” Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign. §11B-502.6 ☐ Parking identification signs shall be reflectorized with a minimum area of 70 square inches. §11B-502.6.1 ☐ Additional language or an additional sign below the International Symbol of Accessibility shall state “Minimum Fine $250.” §11B-502.6.2 ☐ A parking space identification sign shall be visible from each parking space. Signs shall be permanently posted either immediately adjacent to the parking space or within the projected parking space width at the head end of the parking space. Signs may also be permanently posted on a wall at the interior end of the parking space. §11B-502.6.3 ☐ Each accessible car and van space shall have surface identification complying with either of the following schemes: §11B-502.6.4 ☐ The parking space shall be marked with an International Symbol of Accessibility complying with Section 11B-703.7.2.1 International Symbol of Accessibility in white on a blue background a minimum 36 inches wide by 36 inches high. The centerline of the International Symbol of Accessibility shall be a maximum of 6 inches from the centerline of the parking space, its sides parallel to the length of the parking space and its lower corner at, or lower side aligned with, the end of the parking space length. §11B-502.6.4.1 ☐ The parking space shall be outlined or painted blue and shall be marked with an International Symbol of Accessibility complying with Section 11B-703.7.2.1 International Symbol of Accessibility a minimum 36 inches wide by 36 inches high in white or a suitable contrasting color. The centerline of the International Symbol of Accessibility shall be a maximum of 6 inches from the centerline of the parking space, its sides parallel to the length of the parking space and its lower corner at, or lower side aligned with, the end of the parking space. §11B-502.6.4.2 ☐ An additional sign shall be posted either; 1) in a conspicuous place at each entrance to an off-street parking facility or 2) immediately adjacent to on-site accessible parking and visible from each parking space. §11B-502.8 ☐ The additional sign shall not be less than 17 inches wide by 22 inches high. §11B-502.8.1 ☐ The additional sign shall clearly state in letters with a minimum height of 1 inch the following: §11B-502.8.2 "Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or special license plates issued for persons with disabilities will be towed away at the owner’s expense. Towed vehicles may be reclaimedby telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a. ☐ Signs intended for use by pedestrians within parking facilities, including directional or informational signsindicating parking sections or levels, shall comply with the requirements of Section 11B-216. §11B-216.5.2Structural drawings and calculations reviewSheet Z-DN12At grid line “A” and “8”, the footing size should be “F-2”. Calculations reference page 57 & 64.At grid line “C” and “11”, the footing size should be “F-3”. Calculations reference page 57 & 64.Sheet Z-DN14At grid line “D” and “11”, the footing size should be “F-3”. Calculations reference page 57 & 64.At grid line “F” and “between 11&12”, the footing size should be “F-1”. Calculations reference page 57.Per phone conversation on August 31, 2018 with structural engineer, a few braced-frame design in the structural calculations does not match the plan. An updated plan has been reviewed via email. Please include the updated calculations and drawings on the second submittal.