HomeMy WebLinkAbout246635_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10197936
PROJECT ADDRESS:
2008 S Yale St Unit# E
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B
OCCUPANCY CLASSIFICATION(S):
B, F-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/8/2018
INITIAL REVIEW
12/11/2018
EXPIRATION
4/6/2019
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Isaac Karaaslan
3.
TEL:
(714)454-4305
FAX:
VALUATION:$50,000.00
EMAIL:
ampleconstruction@gmail.com
FLOOD ZONE:X-0602320256J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
GENERAL REQUIREMENTSThe drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Building Standards Code with local amendments.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.All persons preparing plans and specificationsshall sign those plans and specifications. This requirement applies to both exempt and non-exempt projects. Business and Professions Code Chapter 3, Division 3, Section 5536.1(a).Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:☒Planning Division approval on the corrected/final set of drawings (647-5804)☒Public Works Agency approval (647-5039)☐Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700)☒Police Department approval on the corrected/final set of drawings (647-5840)☐School District Compliance Certificate; a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout.☒County of Orange Health Department approval on the corrected/final set of drawings (667- 3600)☐Grading Permit - Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039)☒Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance☐Information Technology equipment rooms require a completed electrical plan check prior to issuance of the building permit to ensure compliance with the 2016 California Electrical Code (CEC) Article 645, Electronic Computer/Data Processing Equipment. CEC Article 645 may require fire-rated walls, floors, and ceilings for the computer room(s). For additional information, contact Mr. Scott Davis, Electrical Plan Check at (714) 647-5822.A separate Building Permit Application is required for: Each building, Each structure, Each sign, Trash enclosure(s), Fence(s), Block wall(s), Light standard(s), Pedestrian protection, Demolition, Site improvements, Storage Racks, Screen Wall for Proposed Equipment.State Division of Occupational Safety Permit (Cal/OSHA) (939-0145). A Cal/OSHA permit is required: For construction of trenches or excavations which are 5‘or deeper and into which a person is required to descend. The construction or demolition of any building, structure, false-work, or scaffolding more than three stories high or the equivalent height.Delete all notes and details from drawings that are not a part of the work to be done under the subject building permit application. Clearly indicate the scope of work on the building permit application.Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application.Construction drawings must clearly show all work to be done under the subject building permit application.PLAN REVIEW COMMENTSSheet T-1Revise occupancy group to factory (F-1) and business (B) under Project Data.Verify the square footage of tenant improvement area under Building Area. Floor plan indicates approximately 2,000 square foot remodeling area. However, plan shows 16,032 square foot improvement area.Use a dashed or dotted line to illustrate accessible path of travel from accessible parking spaces to entrance of tenant improvement area. It appears the path of travel encounters a curb ramp near the driveway. Show curb ramp on the site plan and verify existing curb ramp construction complies with accessibility standard.
Sheet A1.0Provide minimum 18-inches strike-edge distance at the latch side of doorway between the office and kitchen.Provide minimum 18-inches strike-edge distance at the latch side of doorway between the offices.Specify door size at the cooler. When doors are open at 90 degree angle at the coolers, the doors shall not reduce the width of hallway width by more than 50%.Provide manufacture specifications and report on proposed coolers.Show exit sign at the end of hallway where exit sign is visible to occupants along the hallway. Current design shows exit signage at the doorway, which is not visible to occupants through line-of-sight at the hallway.Existing restroom does not meet accessibility standard. See checklist below and revise design as necessary.
SIGNS RELATED TO TOILETS AND BATHRING FACILITIES
Item #
Sheet #
Corrections Requested
Respond
☐
Entrances leading to toilet rooms and bathing rooms complying with 11B-603 Toilet and Bathing Rooms shall be identified by a geometric symbol complying with 11B-703.7.2.6 Toilet and Bathing Room Geometric Symbols. Where existing toilet rooms or bathing rooms do not comply with 11B-603 Toilet and Bathing Rooms, directional signs indicating the location of the nearest compliant toilet room or bathing room within the facility shall be provided. Signs shall comply with 11B-703.5 Visual Characters and shall include the International Symbol of Accessibility complying with11B-703.7.2.1 ISA. Where existing toilet rooms orbathing rooms do not comply with 11B-603 Toilet and Bathing Rooms, the toilet rooms or bathing rooms complying with 11B-603 Toilet and Bathing Rooms shall be identified by the International Symbol of Accessibility complying with 11B-703.7.2.1 ISA. Where clustered single user toilet rooms or bathing facilities are permitted to use exceptions to 11B-213.2 Toilet and Bathing Rooms, toilet rooms or bathing facilities complying with 11B-603 Toilet and Bathing Rooms shall be identified by the International Symbol of Accessibility complying with 11B-703.7.2.1 ISA unless all toilet rooms and bathing facilities comply with 11B-603 Toilet and Bathing Rooms. Existing buildings thathave been remodeled to provide specific toilet rooms or bathing rooms for public use that comply with thesebuilding standards shall have the location of and thedirections to these rooms posted in or near the buildinglobby or entrance on a sign complying with 11B-703.5Visual Characters, including the International Symbol ofAccessibility complying with 11B-703.7.2.1 ISA. §11B-216.8
☐
Pictograms shall comply with the following:
☐
Pictograms shall have a field height of 6 inches minimum. Characters and Braille shall not be located in the pictogram field. §11B-703.6.1
☐
Pictograms and their field shall have a non-glare finish. Pictograms shall contrast with their field with either a light pictogram on a dark field or a dark pictogram on a light field. §11B-703.6.2
☐
Pictograms shall have text descriptors located directly below the pictogram field. Text descriptors shall comply with 11B-703.2 Raised Characters,11B-703.3 Braille and 11B-703.4 Installation Heightand Location. §11B-703.6.3
☐
The installation height and location of Pictogram signs shall be per §11B-703.4.1.
☐
Symbols shall comply with the following:
☐
Doorways leading to toilet rooms and bathing rooms shall be identified by a geometric symbol complying with 11B-703.7.2.6 Toilet and Bathing Facilities Geometric Symbols. The symbol shall be mounted at 58 inches minimum and 60 inches maximum above the finish floor or ground surface measured from the centerline of the symbol. Where a door is provided the symbol shall be mounted within 1 inch of the vertical centerline of the door. §11B-703.7.2.6 (See exception)
☐
Men’s toilet and bathing facilities shall be identified by an equilateral triangle, ¼ inch thick with edges 12 inches long and a vertex pointing upward. The triangle symbol shall contrast with the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.1
☐
Women’s toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.2
☐
Unisex toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter with a ¼ inch thick triangle with a vertex pointing upward superimposed on the circle and within the
12-inch diameter. The triangle symbol shall contrast with the circle symbol, either light on a dark background or dark on a light background. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background.§11B-703.7.2.6.3
TOILET AND BATHING ROOM CLEARANCES
Item #
Sheet #
Corrections Requested
Respond
☐
Where toilet facilities and bathing facilities are provided, they shall comply with 11B-213 Toilet Facilities and Bathing Facilities. Where toilet facilities and bathing facilities are provided in facilities permitted by 11B-206.2.3 Multi-Story Buildings and Facilities Exceptions1 and 2 not to connect stories by an accessible route, toilet facilities and bathing facilities shall be provided ona story connected by an accessible route to an accessible entrance. §11B-213.1
☐
Where separate toilet facilities are provided for the exclusive use of separate user groups, the toilet facilities serving each user group shall comply with11B-213 Toilet Facilities and Bathing Facilities. §11B-213.1.1
☐
Where toilet rooms are provided, each toilet room shall comply with 11B-603 Toilet and Bathing Rooms. Where bathing rooms are provided, each bathing room shall comply with 11B-603 Toilet and Bathing Rooms. §11B-213.2 (See exception)
☐
Unisex toilet rooms shall contain not more than one lavatory, and not more than two water closets without urinals or one water closet and one urinal. Unisex bathing rooms shall contain one shower or one shower and one bathtub, one lavatory, and one water closet. Doors to unisex toilet rooms and unisex bathing rooms shall have privacy latches. §11B-213.2.1
☐
Door shall not swing into the clear floor space or clearance required for any fixture. Other than the door to the accessible water closet compartment, a door in any position may encroach into the turning space by 12 inches maximum. §11B-603.2.3
☐
At single user toilet or bathing rooms, doors shall be permitted to swing into the clear floor space or clearance required for any fixture only if a 30 inch by48-inch minimum clear floor space is provided within the room beyond the arc of the door swing. §11B-603.2.3 (See exception)
☐
Mirrors located above the lavatories or countertops shall be installed within the bottom edge of the reflecting surface 40 inches maximum above the finish floor or ground. Mirrors not located above the lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches maximum above the finish floor or ground. §11B-603.3
☐
Coat hooks shall be located within one of the reach ranges specified in Section 11B-308. Shelves shall be located 40 inches minimum and 48 inches maximum above the finish floor. Medicine cabinets shall be located with a usable shelf no higher than 44 inches maximum above the finish floor. §11B-603.4
☐
Where towel or sanitary napkin dispensers, waste receptacles, or other accessories are provided in toilet facilities, at least one of each type shall be located on an accessible route. All operable parts, including coin slots, shall be 40 inches maximum above the finish floor. Baby changing stations are not required to comply with Section 11B-603.5 (See exception) §11B-603.5
☐
Bathtubs shall comply with section 11B-607 including the requirements for clearances, grab bars, seats, controls, shower-spray unit and water and bathtub enclosures.
☐
Shower compartments shall comply with section 11B-608 including the requirements for clearances, grab bars, seats, controls, shower spray unit and water,thresholds, shower enclosures, shower floor or ground surface and soap dish.
WATER CLOSETS AND TOILET COMPARTMENTS
Item #
Sheet #
Corrections Requested
Respond
☐
Where toilet compartments are provided, at least 5 percent but no fewer than one toilet compartment shall comply with Section 11B-604.8.1. In addition to the compartments required to comply with 11B-604.8.1, where six or more toilet compartments are provided, or where the combination of urinals and water closets totals six or more fixtures, toilet compartments complying with Section 11B-604.8.2 shall be provided in the same quantity as the toilet compartments required to comply with Section 11B-604.8.1 §11B-213.3.1
☐
Where water closets are provided, at least 5 percent but no fewer than one shall comply with Section 11B-604. §11B-213.3.2
☐
The water closet shall be positioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 17 inches minimum to 18 inches maximum from the side wall or partition, except that the water closet shall be 17 inches minimum and19 inches maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in Section 11B-604.8.2 Ambulatory Accessible Compartments. Water closets shall be arranged for a left-hand or right-hand approach. §11B-604.2
☐
Clearance around a water closet shall be 60 inches minimum measured perpendicular from the sidewall and 56 inches minimum measured perpendicular from the rear wall. A minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in front of the water closet. §11B-604.3.1
☐
The seat height of a water closet above the finish floor shall be 17 inches minimum and 19 inches maximum measured to the top of the seat. Seats shall not be sprung the return to a lifted position. Seats shall be 2 inches high maximum and a 3-inch high seat shall be permitted only in alterations where the existing fixture is less than 15 inches high. §11B-604.4 (See exception for Residential Units)
☐
The sidewall grab bars shall be 42 inches long minimum, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall with the front end positioned 24 inches minimum in front of the water closet. §11B-604.5.1
☐
The rear grab bar shall be 36 inches long minimum and extend from the centerline of the water closet 12 inches minimum on one side and 24 inches minimum on the other side. §11B-604.5.2 (See exception)
☐
Flush controls shall be hand operated or automatic.Hand operated flush controls shall comply with Section11B-309.4 Operation except they shall be located 44 inches maximum above the floor. Flush controls shallbe located on the open side of the water closet exceptin ambulatory accessible compartments complying with Section 11B-604.8.2 Ambulatory AccessibleCompartments. §11B-604.6
☐
Toilet paper dispensers shall comply with Section 11B-309.4 Operation and shall be 7 inches minimum and 9 inches maximum in front of the water closet measuredto the centerline of the dispenser. The outlet of the dispenser shall be below the grab bar, 19 inchesminimum above the finish floor and shall not be locatedbehind the grab bars. Dispensers shall not be of a type that control delivery or that does not allow continuouspaper flow. §11B-604.7
☐
Wheelchair accessible toilet compartments shall meet the requirements of Sections 11B-604.8.1 Wheelchair Accessible Compartments and 11B-604.8.3 Coat Hooks and Shelves. Compartments containing more than one plumbing fixture shall comply with Section 11B-603 Toilet and Bathing Rooms. Ambulatory accessible compartments shall comply with Sections11B-604.8.2 Ambulatory Accessible Compartments and11B-604.8.3 Coat Hooks and Shelves. §11B-604.8
☐
In a wheelchair accessible compartment with an in- swing door, a minimum 60 inches wide by 36 inches deep maneuvering space shall be provided in front of the clearance required in Section 11B-604.8.1.1Wheelchair Accessible Compartment Size. §11B-604.8.1.1.1, Figures 11B-604.8.1.1.2(b) and 11B-604.8.1.1.3(b)
☐
In a wheelchair accessible compartment with a door located in the side wall or partition, either in-swinging or out-swinging, a minimum 60 inches wide and 60 inches deep maneuvering space shall be provided in front of the water closet. §11B-604.8.1.1.2 Figure 11B-604.8.1.1.2
☐
In a wheel chair accessible compartment with end- opening door located in the front wall or partition (facing water closet), either in-swinging or out-swinging, a minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in front of the water closet. §11B-604.8.1.1.3 Figure 11B-604.8.1.1.3
☐
Toilet compartment doors, including door hardware, shall comply with Section 11B-404 Doors, Doorways, and Gates except that if the approach is from the push side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 48 inches minimum measured perpendicular to the compartment door in its closed position. Door shall be located in front partition or in the side wall or partition farthest from the water closet. §11B-604.8.1.2
☐
Where toilet compartment doors are located in the front partition, the door opening shall be 4 inches maximum from the sidewall or partition farthest from the water closet. Where located in the sidewall or partition, the door opening shall be 4 inches maximum from the front partition and the door shall be self-closing. §11B-604.8.1.2
☐
A door pull complying with Section 11B-404.2.7 Door and Gate Hardware shall be placed on both sides of the door near the latch. Door shall not swing into the clear floor space or clearance required for any fixture. Doors may swing into that portion of the maneuvering space which does not overlap the clearance required at a water closet. §11B-604.8.1.2 (See exception)
☐
At least one side partition shall provide a toe clearance of 9 inches minimum above the finish floor and 6 inches deep minimum beyond the compartment-side face of the partition, exclusive of partition support members. Partition components at toe clearances shall be smooth without sharp edges or abrasive surfaces. Compartments for children’s use shall provide a toe clearance of 12 inches minimum above the finish floor.§11B-604.8.1.4
☐
Ambulatory accessible compartments shall have a depth of 35 inches minimum and 37 inches maximum.§11B-604.8.2.1
☐
Water closets and toilet compartments for children’s use shall comply with Section 11B-604.9 Water Closets and Toilet Compartments for Children’s Use and follow suggested dimensions on Table 11B-604.9. §11B-604.9
☐
Where urinals are provided, at least 10 percent but no fewer than one shall comply with Section 11B-605.§11B-213.3.3.
☐
Urinals shall be the stall-type or the wall-hung type with the rim 17 inches maximum above the finish floor or ground. Urinals shall be 13½ inches deep minimum measured from the outer face of the urinal rim to the back of the fixture. §11B-605.2
☐
Flush controls shall be hand operated or automatic.Hand operated flush controls shall comply with Section11B-309 Operable Parts except that the flush control shall be mounted at a maximum height of 44 inches above the finish floor. §11B-605.4
☐
Where lavatories are provided, at least 10 percent but no fewer than one shall comply with Section 11B-606 and shall not be located in a toilet compartment. §11B-213.3.4, §11B-606.1.
☐
For lavatories and sinks, a clear floor space complying with Section 11B-305 Clear Floor or Ground Surfaces, positioned for a forward approach, and knee and toe clearance complying with Section 11B-306 Knee and Toe Clearance shall be provided. §11B-606.2
☐
Lavatories and sinks shall be installed with the front of the higher of the rim or counter surface 34 inches maximum above the finish floor or ground. §11B-606.3