HomeMy WebLinkAbout245941_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10197730 ACC
PROJECT ADDRESS:
1628 S Grand Ave
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
9/18/2018
Dispensary TI
INITIAL REVIEW
9/28/2018
EXPIRATION
3/17/2019
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Rouzbeh Vahdapour
3.
TEL:
(310)845-5117
FAX:
VALUATION:$106,300.00
EMAIL:
Rooz51@gmail.com
FLOOD ZONE:X-0602320276J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Provide plan check respond sheet. Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3 corrected sets of plans. Please refer to red marks on the drawings for additional plan check comments.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831for an appointment, if needed.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information and submittal requirements. The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (714-647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (714-647-5840)
- Public Works Agency approval (647-5039) Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceReference Sheet AO-1, correct Type of construction to Type V for existing building.Please provide legible Sheet AO.0, and AO.5.Reference Sheet AO.5, correct location of “NO PARKING” to correct location per Section 11B-502.2.3 of 2016 CBCProvide permanent wing wall or railing for drinking fountain per Section 11B-602 of CBC.Show 48” minimum door lading for each door as marked on the drawings including 18”/12” clearance on the push side of the door. Revise drawings to show 34” maximum height for all counter and working tables. Please refer to red marks on the drawings. Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3. Note type of safety glazing complying with CBC Section 2406 for glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24” arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60” above the walking surface.Show/note ventilation requirements on the plans in accordance with the 2016 CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings: mechanical ventilation for each area/room in accordance with the 2016California Mechanical Code to be provided prior to final inspection.Note on drawings: Lighting for each area/room in accordance with the 2016California electrical Code to be provided prior to final inspectionTable 1006.2.1, For Buildings with One Exit: (exiting through office area is not an 2nd exit from Moccupancy). Show path of exit travel on the drawings.Maximum HeightOf BuildingMaximum Occupants
Occupancy Above Grade PlanePer Floor And Travel Distance
A, B, M, 1 Story 49 occupants and 75’ travel distanceIt is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. Please remove notes referring to ADA compliance. This project is reviewed for compliance with 2016 CBC.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Section 202 of Chapter 11B: Valuation of proposed project is estimated at 106,300.00. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access per Section 11B-202 of 2016 CBC for non-compliant elements.
- An accessible entrance
- An accessible route to the altered area
- Accessible restrooms
- Accessible telephone (if any)
- Accessible drinking fountains, and
- Parking, signage and alarmsPlease complete attached accessibility Form and provide a copy on the drawings and submit original Form with revised drawings to Building departmentComplete new ramp detail including top landing and accessible path of travel to east side exit door. Indicate slope and cross slope of ramp and provide truncated doom at bottom of ramp. Show compliance with followings on the drawings:The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors.Provide specifications for doors hardware (push-pull panic) to comply with disabled access requirements. Regardless of the occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall be not more than ½” lower than the threshold of the doorway. Change in level between ¼” and ½” shall be beveled with a slope no greater than 1:2. Change in level greater than ½” shall be accomplished by means of a ramp. Provide detailed sections and plan views showing compliance at all doorways requiring accessibility.All entrances and exterior ground-floor exit doors to buildings and facilities shall be made accessible to persons with disabilities. Doorways shall have a minimum clear opening of 32” with the door open 90 degrees, measure between the face of the door and the opposite stop. Doorways require dimensioning on the plans to insure compliance. Hand-activated door opening hardware shall be centered between 34” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction.Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Tactile exit signs shall be required at the following locations, and show location of each applicable sign on the drawings exiting or accessibility drawings: (show height of tactile sign in compliance with Section 11B-703.4.2.
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”
- Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual
exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 11B-705.
Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 11B-705.For accessible parking and landing show 2% slope in any direction on the drawings.Show location of roof screening on the roof plan and insure that location to match structural drawings.Provide a complete suspended ceiling system plan and section detail showing the following:
- Vertical supports
- Seismic wires
- Seismic strut/Compression strut
- Perimeter wires
- Separate fixture wires for lights and mechanical devices
- ICC Research Report number for the suspended ceilingPlease note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308) OR Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636.Provide structural calculations and drawings, stamped and signed by a California licensed architect or registered civil engineer for:(Incorporate results of structural calculations into drawings prior to re-submittal)
- New roof screening and show location on the roof planIndicate the weight of all existing equipment on the roof plan.Reference detail 6, Sheet S1, please refer to structural drawings to show correct landing for new ramp at door landing. The floor or landing shall be not more than ½” lower than the threshold of the doorway. Reference detail 1, Sheet S1, indicate weight of each new equipment per structural calculations. Subject to inspection by City inspector.