HomeMy WebLinkAbout246041_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10197752 PROJECT ADDRESS: 3700 W Segerstrom Ave Unit# B PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): B, M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 9/20/2018 INITIAL REVIEW 10/2/2018 EXPIRATION 3/19/2019 RECHECKS: 1. 10/30/2018 PROJECT APPLICANT CONTACT PERSON: 2. Ezequiel Pescina 3. TEL: (562)991-9537 FAX: VALUATION:$608,777.00 EMAIL: plansandpermitsexpress@gmail.com FLOOD ZONE:X-0602320258J The recheck of your drawings was completed this morning, 10/30/2018; and the following items from the first plan check are not completed/ done at this time. See the list below for item # 8, 11, 15, 17, & 30. For item # 11, please provide construction details for the proposed man door in the new fence to show full compliance with CBC chapters 10 & 11B. For item # 15, please call out type of hardware for the doors that requires compliance with chapter 11B. For item # 17, provide a detail section and plan view for the threshold to show compliance. For item # 30, there are couple doors that open into the back parking area with any detectable warning. Also, the application for building permit refers to Roof Mounted Equipment. The drawing does not show any new equipment on the roof. Revise the application or provide roof mounted equipment with roof screening for recheck. APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.All drawings and supporting documents shall be prepared, stamped and signed by a California licensed architect or registered civil engineer.All persons preparing plans, specifications, and instruments of service for others shall sign those plans, specifications and other instruments of service for others shall sign those plans, specifications and other instruments of service and all contracts therefore. This requirement applies to both exempt and non-exempt projects. Business and Professions Code Chapter 3, Division 3, Section 5536.1(a).This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Orange County Fire Authority approval on the corrected/final sets of drawings ((714)573-6100) - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceShow on the plans: - Occupancy Classification(s) - Type of Construction - Number of stories/mezzanines and building height in feetProvide on the drawings interior wall and ceiling finish schedule showing compliance with CBC Section 803 and CBC Table 803.11.Exiting from any occupied point in a building or structure on the subject site must be continuous, unobstructed, and undiminished to a public way. This includes gates which must show compliance with CDB Section 1010. Revise drawings to show compliance. Some of the exit doors from this altered area are located behind Wrought Iron Gates. Provide a man door in each of the wrought iron gates to comply with CBC Section 1010 requirements for these exit doors.Provide on the drawings a complete door schedule, showing: - Hardware complying with exiting and disabled accessibility requirementsNote on drawing: “Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort.”The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Show compliance on the drawings for every door in the altered area.Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc) to comply with disabled access requirements.The floor or landing at each side of an exit door shall be level and having a length in the direction of the door swing of at least 60” and the length opposite the direction of door swing of 44” as measured at right angles to the plane of the door in the closed position.Regardless of the occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall be not more than ½” lower than the threshold of the doorway. Change in level between ¼” and ½” shall be beveled with a slope no greater than 1:2. Change in level greater than ½” shall be accomplished by means of a ramp. Provide detailed sections and plan views showing compliance at all doorways requiring accessibility.Hand-activated door opening hardware shall be centered between 34” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction.Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. The bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Is there any exit sign placed for this altered area?Requires exit signs to be readily visible from any direction of approach. No point shall be more than 100’ from the nearest visible exit sign. CBC Section 1008.2.1, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Tactile exit signs shall be required at the following locations: - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Chapter 11B: - An accessible entrance - An accessible route to the altered area - Accessible restrooms - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarmsEntrance(s) to the building or facility and primary path of travel to the specific area of new work, alteration shall be accessible. Path of travel incorporated all elements from the exterior arrival site to remodeled area.Provide construction details on these drawings for the following items to show compliance with CBC chapter 11B: building & site, parking stalls, restrooms, & lockers.Walks and sidewalks shall not have cross slopes exceeding ¼” per foot (2% slope). Slopes along the path of travel shall not exceed 5% unless designed as a pedestrian ramp in accordance with CBC chapter 11B. Walks, sidewalks, and pedestrian ways shall be free of gratings whenever possible. For gratings located in the surface of any of these areas, grid openings in gratings shall be limited to ½” in the direction of traffic flow.If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 11B-247. Show compliance on the drawings.Accessible parking spaces serving a particular building shall be located on the shortest accessible route of travel from adjacent parking to an accessible entrance. Show compliance on the drawings.Surface slopes of accessible parking spaces shall be the minimum possible and shall not exceed 1 unit vertical to 48 units horizontal (2% slope) in any direction.One in every six accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. Show compliance on the drawings.Revise the drawings to show the words NO PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. Sanitary facilities serving the area of new work shall be disabled accessible. Revise the drawings to show compliance with CBC Section11B-604.Provide completely dimensioned floor plans, elevations and sections of sanitary facility insuring wheelchair clearances complying with CBC Section 11B-604 and the California Plumbing Code.Provide complete grab bar details on the drawings showing compliance with CBC structural strength to support a 250 pound point load.Note on the drawings hot water and drain pipes under lavatory shall be insulated.Ensure sanitary facilities comply with CBC Section 11B-604 and that the bottom of the mirror is no higher than 40” from the floor.Every portion of every building in which are installed seats, tables, merchandise, equipment, or similar materials shall be provided with aisles leading to an exit. Every aisle shall not be less than 36” wide if serving only one side, and not less than 44” wide if serving both sides.Show compliance with CBC Sections 11B-227.3 & 11B-904 for the check-in counter. Provide a section at counter that is at least 36” long and no more than 28 to 34” high.Provide construction details for any folding partition in this altered area such as office areas. Also provide structural calculation and construction details for “CO2” tanks & Reservoirs.Please clarify if the sky lights shown on the roof plans are proposed.See other red marks on the drawings. Please resubmit the marked up plans with revised/ updated for recheck.