HomeMy WebLinkAbout244942_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10197422
PROJECT ADDRESS:
809 1/2 E Avalon Ave
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/20/2018
INITIAL REVIEW
8/26/2018
EXPIRATION
2/16/2019
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
James Skurzynski
3.
TEL:
(310)980-6503
FAX:
VALUATION: $56,888.00
EMAIL:
jskurzynski@digmap.com
FLOOD ZONE: X-0602320163JINSTRUCTIONS:
Numbersinbracketsrefertocodesectionsof 2016CaliforniaResidentialCode[CRC],2016CaliforniaBuilding Code[CBC],2016CaliforniaPlumbingCode[CPC],2016CaliforniaMechanicalCode[CMC],2016California ElectricalCode[CEC],2016CaliforniaEnergyCode(2016BuildingEnergyEfficiencyStandards[BEES]),and2016 CaliforniaGreenBuildingsStandardsCode[CalGreen]
Correctoriginaldrawings.Reprintandsubmit3newsetstogetherwiththe“marked-up”set.Returnthiscorrections list with corrected plans.
In the Item number column, ☒ in the checkbox represents correction requested.
IntheRespondcolumn,pleaseindicatethesheetnumberanddetailornote numberontheplanwherethe corrections are made.
Itemize anychanges,revisions,oradditions madeto drawingsthatarenotadirectanswertoa correctionona separate sheet.
Additionalplancheckfeewill be requiredafterthirdreviewonhourlyrate basis.
REFERRALS
Item #
Sheet #
Corrections Requested
Respond
☒
Obtain approvalfromthefollowingdepartments:
☒
PlanningDepartment
☒
Public WorksDepartment
☒
School District
☒
Submitgradingplan forreview.Gradingapprovalisrequiredbeforebuilding permit will beissued.
☒
Geologicalreport/soilreportisrequired.
☒
A1
Providesitedrainageplan.Showsitedrainageslopeanddirection.
☐
Indicateon plan that electricalmeterlocationtobe approvedbyEdison.
PLANREQUIREMENTS
Item #
Sheet #
Corrections Requested
Respond
☒
A1
Showthe correct addressofbuildingonplans. Verify addressing number with Planning Department.[CRCR105.3]
☐
Showthenameand addressoftheownerand personpreparingtheplan.[CRC R105.3]
☒
Structural drawings
Plansandcalculationsshallbestampedand wet signedbyanarchitect or engineerlicensedbytheStateofCalifornia.
☒
A1
Indicateon plan the applicablecurrentcodes:
☒
2016 California Residential Code (CRC)
☒
2016 California Building Code (CBC)
☒
2016 California Plumbing Code (CPC)
☒
2016 California Mechanical Code (CMC)
☒
2016 California Electrical Code (CEC)
☒
2016CaliforniaEnergyCode
☒
2016 California Green Building Standards Code (CalGreen)
☐
Thecurrentdesign codeshavechanged.Pleasesubmitdesign andplansbased on the 2016CRC,2016CBC,2016 CPC,2016CMC,2016CEC,2016 CaliforniaEnergyCode,and 2016CalGreen.
☒
A1
Provideanindexofdrawingson the coversheetofplans.
☒
Everynewlyconstructedbuildingor structuremustshowcompliancewith 2016 CalGreen. Completeand printonplantherequiredmandatorymeasuresforms.See additionalplan checkcommentsfor 2016CalGreen.
☐
Newlyconstructedone-andtwo-familydwellingsand townhouseswith attached garagesshall complywith electric vehicle(EV)charginginfrastructure requirementsinaccordance with2016CalGreenSection4.1.[CRCR309.8]
☐
Newlyconstructedone-andtwo-familydwellingsand townhousesshallinstall anautomaticresidential firesprinklersysteminaccordancewith SectionR313 or NFPA13D.
SITEPLANREQUIREMENTS
Item #
Sheet #
Corrections Requested
Respond
☐
Acompletesiteplan showingpropertylines,lotdimension,yard setbacks,street name(s), north arrow, existing building to remain/removed, distance between buildings and location of private sewage disposal system is required. [CRC R106.2]
☒
A1
On siteplan delineateall projectingelements (roof eaves, balconies, cornices…etc)and showdistanceto property line.[CRCR106.2]
☒
A1
Indicateanyascendingor descendingslopeson thesiteplan.
☒
A1
Showexistingandproposedcontours,spotelevationstoindicategeneralsite slopeand drainagepattern.
☒
A1
Lots shall be graded to drain surface water away from the foundation walls. Where lot lines, walls, slopes or other physical barrier prohibit 6” of fall within 10 ft, drains or swales shall be constructed to ensure drainage away from the structure. [CRC R401.3]
☒
A1
Thegradeshall fall a minimum of 6” within the first 10 feet (5% slope).
☒
A1
Impervious surfaces within 10 feet of the building foundation shall be slope a minimum of 2%away from the building. [CRC R401.3 exception]
BUILDINGLOCATION
Item #
Sheet #
Corrections Requested
Respond
☐
Exterior wallslocated < 3ftfireseparationdistanceshallbe1-hourrated constructionwith exposurefrombothsidesand shallhavenoopening[for nonsprinkleredbuildingper CRCTableR302.1(1)].
☐
Exterior wallslocated 3ftto<5ftfireseparationdistanceshallbe1- hourrated constructionwith exposurefrombothsidesand shallhave25%max.ofwallareaopenings[fornonsprinkleredbuildingper CRCTableR302.1(1)].
☒
A1
☐
Projections(e.g. eave overhangs or cornices) with < 2ft fireseparation distanceis not allowed [fornonsprinklered building per CRC Table R302.1(1)].
☒
Projections(e.g. eave overhangs or cornices) with ≥ 2ft to <5ft fire separation distanceshall be 1-hourrated on the undersideOR provide fire blocking fromthewall top plate tothe underside ofroofsheathing and gable vent openings are notinstalled [fornonsprinklered building per CRC TableR302.1(1)].
☐
Penetrationslocated <3ftfireseparationdistanceshall complywith Section R302.4.
☐
Exterior walls located < 3ft fire separation distance shall be 1- hour ratedconstruction with exposure from the outside and shall have no opening [forsprinklered building per CRC Table R302.1(2)].
For residential subdivisions where all dwellings are equipped with an automatic sprinkler system installed inaccordance with Section R313, thefire separation distance for nonrated walls and rated projections shall be permitted toreduce to 0feet, and unlimited unprotected openings and penetration shall be permitted, where the adjoining lot provides an open setback yard that is 6feet or more inwidth on the opposite side of the property line. [CRC Table R302.1(2) footnote a]
☐
☐
Projections(e.g. eave overhangs or cornices) with < 2ft fire separationdistanceis not allowed [for sprinklered building per CRC Table R302.1(2)].
☐
Projections(e.g. eave overhangs or cornices) with ≥ 2ft to <3ft fire separation distanceshall be 1-hourrated on the undersideOR provide fire blocking fromthewall top plate tothe underside ofroofsheathing and gable vent openings are notinstalled [for sprinklered building per CRC TableR302.1(2)].
☐
Detached garagesaccessorytoa dwellinglocatedwithin2ftofa lot line are permittedto haveroofeaveprojectionsnot exceeding4”.[CRCR302.1 exceptions4]
☐
Buildingsadjacenttoascendingor descendingslopessteeperthan 33.3%(1 unit vertical in3unitshorizontal)shallbesetbackaccordingtotherequirementsof CRCSectionR403.1.7andFigureR403.1.7.1.
ROOFCOVER
Item #
Sheet #
Corrections Requested
Respond
☒
A1
For roofcoveringspecify[CRCR902,R905]:
☒
Manufacturerand ICC/UL/FMnumber
☐
Roofslopeofallareason theroofplan
☒
Noteonplan thatinstallationshallbeinaccordance with manufacturer’s specifications
☐
Roofslopeisnot adequatefor Typeofroofcovering specified.[CRCR905.2–R905.16]
☐
Showsizes and locationsoftheroof/deckdrainsandsecondaryemergency overflowroofdrainsor scuppers.[CRCR903.4.1,CPC1101.12and CPC 1102.0]
☐
Specifyapproved weatherproofwalkingsurfacematerial at decksandbalconies. ProvideICC/ULnumber.
DESIGNREQUIREMENTS
Item #
Sheet #
Corrections Requested
Respond
☐
Habitablerooms,otherthan kitchen,shall contain atleast 70 squarefeet offloor area. [CRCR304.1]
☐
Habitablerooms,otherthan a kitchen,shall notbelessthan7ft. in any horizontaldimension.[CRC304.2]
☐
Habitablespaces,hallways,and portionsofbasementscontainingthesespaces shallhavea minimumof7ft. ceilingheight.[CRCR305.1
☐
Bathrooms,toilet roomsand laundryroomsshallhaveaminimumof6’-8” ceilingheight.[CRCR305.1]
☐
For roomswith sloped ceilings,therequired floorareaoftheroomshallhavea ceilingheightofnotlessthan 5ft. andnotlessthan50%oftherequired floor areashallhavea ceilingofnotlessthan7ft.[CRCR305.1exception1]
☐
Ashoweror tub equipped with ashowerheadshallhavea minimumof6’-8” ceilingheightabovea minimumareaof30”x30”attheshowerhead[CRC R305.1exceptions2].
☐
Beams,girders,ductsorotherobstructionsinbasementscontaininghabitable spacesshallbepermittedtoprojecttowithin6’-4”ofthefinishfloor.[CRC R305exception3]
☐
Portionsofbasementsthat do notcontainhabitablespacesorhallwaysshall haveaminimum6’-8”ceilingheight.[CRCR305.1.1]
☐
Windowareaofhabitableroomsmustbe atleast 8%oftheroomfloorarea fornaturallight,orprovideartificial light.[CRCR303.1]
Artificiallightmustbe capableproducinganaverageilluminationof6 footcandlesover areaoftheroomat heightof30 inchesabovefloor[CRC R303.1exceptions2].
☐
Openablewindowareaofhabitableroomsmustbe atleast 4%oftheroom floorareafornatural ventilation,or providea whole-housemechanical ventilationsysteminstalledinaccordance with CMC.[CRCR 303.1 exceptions1]
☐
Useofsunroomsand patio coversshallbepermitted fornaturalventilationifat least 40%ofsunroomwallsareopenorare enclosedonlybyinsectscreen,and the ceilingheightofsunroomis notlessthan 7’[CRCR303.1exceptions3, R303.8.1].
☐
At least ½ofthe common wall between mustbeopenand havean unobstructedopeningareaofnotlessthan 25 sqftor 10%ofthefloor areaoftheinterior room, whicheveris greater,iflight and ventilationisbeing supplied fromanadjacentroom[CRCR303.2].
☒
A1
Each bathroomcontaininga bathtub, showeror a spashallbemechanically ventilatedwith a minimum50 cfmintermittentor 20 cfmcontinuousexhaust fan [CRCR303.3.1,CMCTable403.7].The fan mustbe controlledbya humiditycontrol.[CalGreen4.506.1item2]
☒
A1
Water closetshallbesetno closerthan15” fromits centertoanyside wall or obstructionornocloserthan 30”centertocentertoanysimilar fixture and the clear spaceinfrontofa water closet,lavatory,or a bidetshallbe atleast 24”[CPC402.5].
☐
Urinalshallbeset no closerthan12” fromits center toanysidewall orpartition or no closerthan24”center tocenter[CPC402.5]
☐
Showerfloorsand wallsabovebathtubswith installedshowerhead shallbe finishedwith a nonabsorbentsurfacetoa heightnotlessthan6ftabovethe floor.[CRCR307.2]
☐
Net areaofshowercompartmentsshallbenotlessthan1,024sq.in. offloor area, and encompass30 inchdiametercircle. [CPC408.6]
☒
A1
4040SL
Near entrance
Safetyglazing(temperedglazing)isrequired forthefollowing:
☒
Wherethe glazingis within 24" of either side ofthe door in the plane of thedoor ina closed position and wherethe bottom edge ofthe glazingisless than 60” abovethe floor. [CRC R308.4.2 item 1]
☐
Wherethe glazingis on a wall perpendicular to the plane ofthe doorina closed position and within 24” ofthe hingeside of an in-swinging door. [CRC R308.4.2item 2]
☐
Glazinglessthan 60" abovea shower or tub floor. [CRCR308.4.5]
☐
Glazing wherethe bottom edgeislessthan 36” abovethestairways, landings, and ramps. [CRCR308.4.6]
☐
Glazing adjacentto thestairway bottomlanding wherethe glazingisless than 36” abovethelanding and within 60” horizontal arclessthan 180 degrees fromthe bottomtread nosingshall besafety glazing. [CRC R308.4.7]
☐
Providedetailsand/ornotesfor1-hourfire-resistanceconstructionofwallsand floorseparatingdwellingunitsfornonsprinkleredbuildingor1/2-hourfire- resistanceconstructionforsprinkleredbuilding.[CRCR302.3]
☐
At bedrooms,habitableattics, and basementsprovideoneoperableemergency escapeand rescuewindowor doormeetingall ofthefollowing:anopenable area ofnotlessthan5.7 sqft(5 sqft atgradelevel),a minimumclear 24inchheightand20 inch width,anda maximum44 inches measuredfromthefloor to the bottomofthe clear opening.[CRCR310.1,R310.2.2]
☐
Windowfall protectionshallbeprovided wherethetopofthesillofan operable windowopeningislocated lessthan 24”abovethefinished floorand greater than72”abovethefinishedgradeorothersurfacebelowon the exteriorofthe building.Theoperable windowswith openingssuchthat a 4inchspherecannot pass,orprovidewindowfall preventiondeviceor windowopeningcontrol devicesthat complywith ASTMF2090.[CRCR312.2]
☐
Showlocationofhardwiredsmokealarms[CRCR314.3]:
☐
In eachsleepingroom
☐
Outside each separate sleeping area in the immediate vicinity of the bedrooms
☐
On eachstory,basement,andhabitableattics
☐
Minimum3ft.fromthedoororopeningofabathroomthatcontainsa bathtubor shower
☐
Noteonplan smokealarmsshall complywith specificlocation requirementsper NFPA72 Section 29.8.3.4.[CRCR314.3.3]
☒
A1
Showlocationofhardwired carbonmonoxidealarms[CRCR315.3]:
☒
Outside of each separate sleeping area in the immediate vicinity of the bedrooms
☒
On everyoccupiablelevel ofa dwellingunit,includingbasements
☒
Whereafuel-burning applianceislocatedwithinabedroomoritsattached bathroom,a carbonmonoxidealarmshallbeinstalledwithinthebedroom
☒
Noteonplan smokealarmrequirements:
☒
An approvedsmoke alarmshall beinstalled for new construction and alteration,repair or additionsrequiring permit exceeding $1000. [CRC R314.2.2, R314.8.2.a.1]
☒
Battery operatedsmoke alarms permittedin existing buildings where no construction istaking place or in building undergoing alteration orrepair that do notresult in theremoval ofinterior walls or ceiling finishes, unless thereis an attic, crawlspace or basement which could provide access for wiring. [CRCR314.6 exceptions 1, 3]
☒
Smokealarmsshallbeinterconnectedsuchthat the activationofonealarm will activate allalarmsintheindividualdwellingunit.[CRCR314.4]
☒
Smokedetectorsshallbe “hard wired”and shallbeequippedwithbattery backup.[CRCR314.6]
☒
A1
Noteonplan carbonmonoxidealarmrequirements:
☒
CO alarmsshall be “hard wired” and shall be equipped with battery backup. [CRC R315.5]
☒
CO alarmsshallbelisted inaccordance with UL2034[CRCR315.1.1].
☒
CO detectorshall belistedin accordance with UL 2075 [CRC R315.6.1].
☒
CO alarmsshall beinterconnected suchthatthe activation of one alarm will activate allalarmsintheindividualdwellingunit.[CRCR315.7]
☒
In existing dwellingunita CO alarmis permittedto be battery operated whererepair or alteration do not resultintheremoval of wall or ceiling finishes. [CRC R315.5 exceptions 4.2]
☒
Provide22”x 30”attic accessfor attic areasthat havea vertical heightof≥30” over anareaonnotlessthan30sqftlocated inhallwayor otherreadily accessiblelocation.[CRCR807.1]
☐
Provide22”x 30”minimumaccessopeningandpassagewayor atleast aslarge asthelargest componentoftheappliance wheremechanicalequipmentlocated inatticor under-floorspace.[CMC304.4]
☐
Providefullheightcrosssectioncrosssectionthroughshowing framing,interior/exteriorsheathing,plateheight,insulation,foundation,finish grade,etc.
☒
A1
Showhowdwellingisprovidedwith heatingfacilitycapableof maintaininga minimumroomtemperatureof68°F ata point3ftabovethefloorand2ftfrom exteriorwallsofhabitablerooms.[CRCR303.9]
☐
Provide&detaildraft-stopsinconcealedspaceofafloor/ceilingassemblyso that the areaofthe concealedspacedoesnot exceed 1000ft2anddividethe concealedspaceintoapproximatelyequal areas.[CRCR302.12,R502.12]
MEANSOFEGRESS
Item #
Sheet #
Corrections Requested
Respond
☒
A1
At least one egress door shall be provided for each dwelling unit. Show location of required egress door. [CRC R311.2]
☐
The means of egress shall not travel through a garage to the egress door. Revise design as necessary. [CRC R311.1]
☐
The required egress door shall open directly into a public way or to a yard or court that opens to a public way. Revise design as necessary. [CRC R311.1]
☒
A1
Egress door shall comply with the following requirements: [CRCR311.2]
☒
Side-hinged door type. Specify door type on door schedule.
☒
2’-8” minimum clear width measured between the face of door and the stop, with the door opens 90 degrees. Specify egress door width on door schedule.
☒
6’-6” minimum clear height measured from top of threshold to bottom of stop. Specify egress door height on door schedule.
☒
Specify the type of latching/ locking hardware, or provide note: “Egress doors shall be readily openable from inside the dwelling unit without the use of a key or special knowledge or effort.”
☒
A1
Landings at exterior doors shall comply with the following requirements: [CRC R311.3]
☒
Show a landing on the outsideofexteriordoors
☒
Provide dimensional lines at exterior landings
☒
The landing width shall not be less than the door served.
☒
The landing length measuredindirectionoftravel shallnot be lessthan36 inches.
☒
Provide note: “The slope at exterior landings shall not exceed ¼ unit vertical in 12 units horizontal (2 percent)”.
☒
Specify elevation difference between the exterior door and top of threshold.
☐
The landing on exterior side shall not be more than 7 ¾ inches below top of threshold provided the door does not swing over the landing.
☐
The landing on exterior side shall not be more than 1 ½ inches below top of threshold with the door swings over the landing.
☐
Exteriorbalconieslessthan60square feet accessible froma doorarepermittedto have a landinglessthan36” inthedirectionoftravel.[CRCR311.3exception]
☐
All exterior doors except the required egress door:
☐
A top landing is not required where a stairway of not more than two risers is located on the exterior side of the non-required egress door, provided that the door does not swing over the stairway. [CRC R311.3.2 Exception].
☐
Provide a top landing not more than 7 ¾” below the top of threshold for stairway of more than two risers at the exterior side of the non-required egress door, provided that the door does not swing over the stairway. [CRC R311.3.2 Exception].
☐
Provide a top landing not more than 1 ½” below the top of threshold for stairway of more than two risers at the exterior side of the non-required egress door, with the door swing over the stairway. [CRC R311.3.2 Exception].
☐
Forhabitablelevelsor basementslocated morethan onestoryaboveor more thanonestorybelowanegressdoor,themaximumtravel distancefromany occupiedpointtoa stairwayor rampthat provideegressfromsuchhabitable level or basementshall not exceed 50 ft.Provide a dimensional line from the most remote occupied point to a stairway or ramp. [CRCR311.4]
☐
Specify width dimension in hallway. The minimumwidthofa hallwayshallbenotlessthan3feet.[CRCR311.6]
VENTILATION
Item #
Sheet #
Corrections Requested
Respond
☒
A1
Showonplantherequiredattic ventilationsize, type, and location.
☒
A1
Provide calculations on attic-ventilation area. Theminimumrequirednet free ventilatingarearatio is [CRCR806.2]:
☒
A1
☒
1/150ofattic area, or
☐
1/300ofattic areaifatleast 40%and notmorethan50%oftherequired ventilatingareaisprovidedwithventilatorlocatedintheupperportionof the attic orrafterspace3feetmaximumbelowtheridgeorthehighestpoint.
☒
A1
Provide note: “Ventilation openings shall have a least dimension of inch minimum and ¼ inch maximum. Ventilation openings having a least dimension larger than ¼ inch shall be provided with corrosion-resistant wire cloth screening, hardware cloth or similar material with openings having a least dimension of 1/16 inch minimum and ¼ inch maximum.”
☐
Aminimumofone inchofspaceshallbeprovidedbetweentheinsulationand theroof sheathingandatthelocationofvents[CRCR806.3].At vaulted ceilingor flat roofs,detail ventilation forspacebetweenindividualroofjoists.
☐
Showonplantherequiredunder-floorventilationsize, type, and location.
☐
One under-floor ventilation opening shall be within 3 feet of each corner of the building. Show under-floor ventilation locations on plan. [CRCR408.2]
☐
Provide calculations on under-floor ventilation area. Theminimumrequirednet free ventilatingarearatio is [CRCR408.2]:
☐
☐
1/150ofunder-floorarea, or
☐
1/1,500 of under-floor area where the ground surface is covered with an approved Class I vapor retarder material and the required openings are placed to provide cross ventilation of the space.
☐
Ventilation openings shall be covered for their height and width with any of the following materials provided that the least dimension of the covering shall not exceed ¼ inch. Specify the type of ventilation-cover material on plan: [CRCR408.2]
☐
Perforated sheet metal plates not less than 0.070 inch thick
☐
Expanded sheet metal plates not less than 0.047 inch thick
☐
Cast-Iron grill or grating
☐
Extruded load-bearing brick vents
☐
Hardware cloth of 0.035 inch wire or heavier
☐
Corrosion-resistant wire mesh, with the least dimension being 1/8 inch thick
WATERHEATER
Item #
Sheet #
Corrections Requested
Respond
☐
Showlocationwaterheater on floorplan.
☒
A1
The minimumcapacity forwater heatersshallbeinaccordance with thefirst-hourratinglisted inCPC Table501.1(1).Printonplan CPC Table501.1(1).
☐
Showhowheat producingappliances(waterheater/dryer/furnace)ingarage will beprotectedfromautomobiledamage(wheelblocksarenotsufficient). Elementsofappliances which createa glow,spark,or flameshall belocated a minimumof18"abovegarage floorunlesslisted asflammablevaporignition resistance.[CMC305.1,305.1.1]
☒
A1
Waterheatersshallbe anchoredor strappedtothestructure.[CPC507.2]. Showsize and locationofstraps,connector,etc.
☒
A1
Whena waterheater islocated inthe attic,attic-ceilingassembly,floor-ceiling assembly,or floor-subfloorassemblywheredamagemayresultfroma leaking waterheater,a watertightpanofcorrosion-resistantmaterialsshallbeinstalled beneaththewaterheaterwith a minimumthree-quarter(3/4) inch (20 mm) diameterdrain toanapprovedlocation.Suchpanshallnotbelessthan 1½” in depth.[CPC507.5]
☒
A1
Showsourceofcombustionair forwaterheater.[CMC701.0,CPC506.0]
☒
A1
Addthefollowingnoteonplan:
EffectiveJan 1, 2017newinstallationgaswaterheater shallhaveallthe followingasper 2016 EnergyStandards150.0(n):
1) A120Velectrical receptacleiswithin3feet fromthewaterheater and accessiblewith noobstructions.
2) ACategoryIIIor IVvent,ora TypeB ventwith straightpipebetween outsideandwaterheater.
3) Acondensatedrainnomorethan2incheshigher than thebaseonwater
heater fornaturaldraining.
4) Agassupplylinewith capacityofatleast 200,000Btu/hr.
MECHANICAL/ELECTRICAL/PLUMBING
Item #
Sheet #
Corrections Requested
Respond
☒
A1
ShowlocationofF.A.U./returnair grill /waterheater on floorplan.
☒
A1
Showa level workingplatformnotlessthan 30”x30"infrontoftheservice sideoffurnace.[CMC304.4.3]
☒
A1
Accesstoattic furnacemustbewithin20 feet ofunit and shallhavea continuoussolidwalkwayatleast 24inches wide.A120-voltreceptacleoutlets and a switch controlledlightis also required.[CMC304.4.1,2,4]
☒
A1
Showsourceofcombustionair tofurnaceand waterheater.[CMC701.1,CPC 506.0]
☒
A1
Providetype1clothesdryerexhaustduct(min.4inchdia. And0.016”thick rigid metal)tothe outsideofthe buildingandequipped with a back-draft damper.Exhaustductlengthislimited to 14 ft. with 2elbows.[CMC504.2, 504.4.2.1,504.4]
☒
A1
a) Provide100squareinchesof makeupair for clothesdryercloset.[CMC 504.4.1item(1)]
b) Type1clothesdryerexhaustductshallbeprovided with makeupair in accordance with themanufacturerinstructions.[CMC504.4.1item(1)]
c) Type2clothesdryersshallbeprovided with makeupair openingsof1 squareinch for each 1,000Btu/htotal inputratingofdryerinstalled.[CMC
504.4.1item(2)]
☒
A1
All hosebibs musthaveanapprovedanti-siphondevice.[CPC603.5.7]
☒
A1
Showelevationsoffinishfloorand nearest upstreammanhole.Showthat finish flooris aboveupstreammanholeor providebackwater valveper CPC710.1. Notethat fixturesabovesuch elevationshall notdischargethroughthe backwatervalve.
☒
A1
Under-floorcleanoutshallbelocated notexceeding5’ fromanaccessdoor, doortrap,or crawlhole.[CPC707.9]
☒
A1
a) Showsize and locationofelectrical serviceand panels.Providepanel schedulesandsinglelinediagramsforservicesof400ampand greater.
b) Noteonplan thatlocationofelectrical servicepanelmustbe approvedby
Edison.
☒
A1
ProvideUFERorotherapprovedground.[CEC250.50]
☐
Oneswitchedlightfixtureor switchlightingoutletshallbeinstalledin every habitableroom,bathroom,stairway,hallways,attached garage,detached garage with electricpower,at outdoorentrancesor exits,interiorstairways,attics, underfloorspaces,utilityrooms, and basements.[CEC210.70(A)]
☐
Interiorstairwaysshall be provided with artificial lightsourcetoilluminate thelandings andtreads, capable ofilluminatingtreads and landings atleast 1 foot candle measured atthe center oftreads and landings. [CRCR303.7].
Exteriorstairwaysshall be provided with artificial lightsourcelocated at the top landing ofthestairway [CRCR303.8].
Providea wall switch at each floorlevel to controllighting forstairway with six or morerisers. [CRCR303.7]
☒
A1
Provide atleast one outdoor weatherproof GFCIreceptacle at front and back of dwelling unit, not morethan 6½ftabove grade. [CEC 210.52(E)(1) and 210.8(A)(3)] Receptaclesin wet locations must havea listed “extra duty” cover. [CEC406.9(B)(1)]
☒
A1
Provideatleast oneweatherproofGFCIreceptacle forbalconies,decks,and porchesthat are attached tothedwellingunit and are accessible frominsidethe dwellingunit.Thereceptacleshallnotbelocated morethan6½’abovethe balcony,deck,or porchwalkingsurface.[CEC210.52(E)(3),210.8(A)(3)]
☐
a) Provideatleast onereceptacle(in additionto anyreceptacleprovidedfor specificequipment)inattached garage,unfinishedportionofbasement,or ineach detachedgarageor accessorybuildingwith electricpower.[CEC 210.52(G)]
b) Thebranch circuit supplyingthe garagereceptaclesshallnotsupplyoutlets outsideofthe garage.[CEC210.52(G)(1)]
c) Provideatleast onereceptacleoutletinstalledingarage for eachcar space. [CEC210.52(G)(1)]
☐
ProvideGFCIprotectiontoall 125volt,15 and 20 amp receptacles installedinbathrooms,outdoors,inunfinishedbasements,atkitchen countertopsurface,within6’ofsink,within6’ ofbath tubsor showerstall, laundryareas, and garages.[CEC210.8(A)]
ProvideGFCIprotection foroutletsthat supplydishwashers.[CEC 210.8(D)]
☐
Walls2feet wideor greatershallhavean outlet.Outletsshallbespacedno morethan 12 feet apart, and a maximumof6feetfromend of wallsor opening. [CEC210.52(A)]
☐
Provideatleast onereceptacleoutletforhallwaysover10 ft inlength.[CEC 210.52(H)]
☐
Foyersthat arenotpartofa hallwayhavinganarea>60 ft2arerequiredtohave receptacle(s)located ineachwall space3ftor moreinwidth.[CEC210.52(I)]
☒
A1
In the kitchen,pantries,breakfastrooms,and diningrooms,a receptacleshallbe providedfor eachwall countertopspacewiderthan 12 inchesso that nopointis morethan 24"froman outlet.[CEC210.52(C)]
☒
A1
Noteonplan:Theminimumclearancebetweenluminariesinstalledinclothes closetsand thenearest pointofa closetstoragespaceshallbeperCEC410.16 &Figure410.2:
a) 12” forsurface-mountedincandescentor LEDluminarieswith a
completelyenclosedlightsourceinstalledonthewall abovethe doororon the ceiling.
b) 6”forsurface-mountedfluorescentluminariesinstalled on thewallabove
the doororonthe ceiling.
c) 6”forrecessedincandescentor LEDluminarieswith a completely enclosedlightsourceinstalledinthewall or the ceiling.
d) 6”forrecessedfluorescentluminariesinstalledinthewall or ceiling.
e) Surface-mountedfluorescentorLEDluminariesshallbepermittedto be installedwithinthe closetstoragespacewhereidentifiedforsuchuse.
☐
Wherethe electrical serviceislocated in/onthe attached garageand a furred garage wall isthemethodusedtorun the non-metallicsheathed cablestothe residencethroughthefirewall,providea detail showinghowthe penetration will befirestopped.[CEC300.21]
☒
A1
All branch circuits that supply120volt,singlephase,15and20 ampereoutlets installedindwellingunitfamilyrooms,kitchens,diningrooms,livingrooms, parlors,libraries,dens,bedrooms,sunrooms,recreationrooms,closets,
hallways,laundryareas,or similarroomsor areasshallbeprotectedbya listed
arc-faultcircuit interruptercombinationtype[CEC210.12(A)].
☐
All nonlockingtype125-volt,15and 20 Ampreceptaclesina dwellingunit shallbelisted tamper-resistantreceptacle exceptforreceptacleslocated more than5½’abovethefloor.[CEC406.12]
☒
A1
Refrigerantserviceportslocatedoutdoorsshallbefitted with locking-type tamper-resistantcaps.[CMC1105.11]
☐
Water closetsshallhaveaneffective flush volumeof1.28 gallonsmax.of water per flush.[CPC411.2]
ADDITIONALCORRECTIONS
Item #
Sheet #
Corrections Requested
Respond
☒
A1
Keynotes on site plan do not match the Plan Notes
☒
A1
Verify code reference on detail one. Uniform Building Code (UBC) is an outdated reference.
☒
A1
Revise occupancy group to “R-3”.
☒
A1
Revise maximum flash rate “1.28” at plumbing fixtures.
☒
A1
Revise keynote number to “15” on roof plan.
☒
Provide energy documentations for review.
☒
Provide soils report for review.
☒
Submit grading plans to Public Works department for review.
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐
☐