HomeMy WebLinkAbout248680_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10198522 PROJECT ADDRESS: 2110 S Yale St Unit# B PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/29/2018 INITIAL REVIEW 12/9/2018 EXPIRATION 5/28/2019 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Vivian Khong 3. TEL: (714)717-9896 FAX: VALUATION:$241,248.00 EMAIL: VIkhong1@yahoo.com FLOOD ZONE:X-0602320256J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS GENERAL REQUIREMENTSThe drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Building Standards Code with local amendments.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.All persons preparing plans and specificationsshall sign those plans and specifications. This requirement applies to both exempt and non-exempt projects. Business and Professions Code Chapter 3, Division 3, Section 5536.1(a).Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:☒Planning Division approval on the corrected/final set of drawings (647-5804)☒Public Works Agency approval (647-5039)☒Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700)☒Police Department approval on the corrected/final set of drawings (647-5840)☐School District Compliance Certificate; a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout.☐County of Orange Health Department approval on the corrected/final set of drawings (667- 3600)☐Grading Permit - Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039)☒Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance☐Information Technology equipment rooms require a completed electrical plan check prior to issuance of the building permit to ensure compliance with the 2016 California Electrical Code (CEC) Article 645, Electronic Computer/Data Processing Equipment. CEC Article 645 may require fire-rated walls, floors, and ceilings for the computer room(s). For additional information, contact Mr. Scott Davis, Electrical Plan Check at (714) 647-5822.A separate Building Permit Application is required for: Each building, Each structure, Each sign, Trash enclosure(s), Fence(s), Block wall(s), Light standard(s), Pedestrian protection, Demolition, Site improvements, Storage Racks, Screen Wall for Proposed Equipment.State Division of Occupational Safety Permit (Cal/OSHA) (939-0145). A Cal/OSHA permit is required: For construction of trenches or excavations which are 5‘or deeper and into which a person is required to descend. The construction or demolition of any building, structure, false-work, or scaffolding more than three stories high or the equivalent height.Delete all notes and details from drawings that are not a part of the work to be done under the subject building permit application. Clearly indicate the scope of work on the building permit application.Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application.Construction drawings must clearly show all work to be done under the subject building permit application. PLAN REVIEW COMMENTS Sheet SP.1Revise the occupancy groups to “Business (B), Factory (F-1), and Storage (S-1)” under Site General Notes.Revise the type of construction to “III-B” under Site General Notes.Show the Path of Travel from accessible parking spaces to entrance of suite B.Provide and cross reference site accessibility elements. For example, accessible parking spaces, signage, access aisle. See checklist below for accessibility requirements. PARKING SPACES Item # Sheet # Corrections Requested Respond ☐ Where parking spaces are provided, accessible parking spaces shall be provided in number and kind required per Section 11B-208 Parking Spaces. §11B-208.1 ☐ Provide ( ) accessible parking spaces as required byTable 11B-208.2. §11B-208.2 (See exceptions) ☐ Provide accessible spaces for each parking facility (parking lots and parking structures). The number of parking spaces required to be accessible is to be calculated separately for each parking facility; the required number is not based on the total number of parking spaces provided in all of the parking facilities provided on site. §11B-208 ☐ Ten percent of patient and visitor parking spaces provided to serve hospital outpatient facilities, and free- standing buildings providing outpatient clinical services of a hospital, shall comply with Section 11B-502Parking Spaces. §11B-208.2.1 ☐ Twenty percent of patient and visitor parking spaces provided to serve rehabilitation facilities specializing in treating conditions that affect mobility and outpatient physical therapy facilities shall comply with Section11B-502 Parking Spaces. §11B-208.2.2 ☐ One in every six or fraction of six parking spaces required by Section 11B-208.2 Minimum Number, but not less than one, shall be served by an access aisle 96 inches wide minimum placed on the side opposite the driver’s side when the vehicle is going forward into the parking space and shall be designated “vanaccessible”. All such spaces may be grouped on one Level of a parking structure. §11B-208.2.4, 11B-502, Fig 11B-502, 11B-502.3, & 11B-502.3.3 ☐ Accessible parking spaces complying with Section 11B- 502 Parking Spaces serving a particular building or facility shall be located on the shortest accessible routeof travel from adjacent parking to an accessible Entrance (as near as practical to an accessible entrance). §11B-208.3.1 ☐ In buildings with multiple accessible entrances with adjacent parking, accessible parking spaces complying with Section 11B-502 Parking Spaces shall be dispersed and located closest to the accessible entrances. §11B-208.3.1 ☐ In parking facilities that do not serve a particular building or facility, accessible parking spaces complyingwith Section 11B-502 Parking Spaces shall be located on the shortest accessible route of travel to an accessible pedestrian entrance of the parking facility.§11B-208.3.1 ☐ Dimension minimum 18-foot long car and van accessible parking space(s) and access aisle(s). §11B-502.2, Figures 11B-502.2 and 11B-502.3 ☐ Dimension minimum 9-foot width at accessible car parking space. §11B-502.2, Fig. 11B-502.2 & Fig.11B-502.3 ☐ Dimension minimum 12-foot wide accessible van parking space with minimum 5-foot wide access aisle. Van parking spaces shall be permitted to be minimum 9 feet wide where access aisle is 8-foot wide minimum.§11B-502.2, Figures 11B-502.2 and 11B-502.3 ☐ Car and van stall access aisle shall be 5 foot wide minimum and shall adjoin an accessible route. Two parking spaces shall be permitted to share a common access aisle. §11B-502.3, Figures 11B-502.2 and11B-502.3 ☐ Access aisles shall be marked with a blue painted borderline around their perimeter. The area within the blue borderlines shall be marked with hatched lines a maximum of 36 inches on center in a color contrasting with that of the aisle surface, preferably blue or white. The words "NO PARKING" shall be painted on the surface within each access aisle in white letters a minimum of 12 inches in height and located to be visible from the adjacent vehicular way. Access aisle markings may extend beyond the minimum required length. §11B-502.3.3, Figure 11B-502.3.3 ☐ Access aisles shall not overlap the vehicular way.Access aisles shall be permitted to be placed on either side of the parking space except for van parking spaces which shall have access aisles located on the passenger side of the parking spaces. §11B-502.3.4 ☐ Clearly show minimum vertical clearance of 8 feet 2 inches at accessible parking spaces and along at least one vehicle access route to such spaces from site entrances and exits. §11B-502.5 ☐ Parking space identification signs shall include the International Symbol of Accessibility complying with Section11B-703.7.2.1 International Symbol of Accessibility. §11B-502.6, Figure 11B-703.7.2.1 ☐ Signs identifying van parking spaces shall contain additional language or an additional sign with the designation “van accessible.” Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign. §11B-502.6 ☐ Parking identification signs shall be reflectorized with a minimum area of 70 square inches. §11B-502.6.1 ☐ Additional language or an additional sign below the International Symbol of Accessibility shall state “Minimum Fine $250.” §11B-502.6.2 ☐ A parking space identification sign shall be visible from each parking space. Signs shall be permanently posted either immediately adjacent to the parking space or within the projected parking space width at the head end of the parking space. Signs may also be permanently posted on a wall at the interior end of the parking space. §11B-502.6.3 ☐ Each accessible car and van space shall have surface identification complying with either of the following schemes: §11B-502.6.4 ☐ The parking space shall be marked with an International Symbol of Accessibility complying with Section 11B-703.7.2.1 International Symbol of Accessibility in white on a blue background a minimum 36 inches wide by 36 inches high. The centerline of the International Symbol of Accessibility shall be a maximum of 6 inches from the centerline of the parking space, its sides parallel to the length of the parking space and its lower corner at, or lower side aligned with, the end of the parking space length. §11B-502.6.4.1 ☐ The parking space shall be outlined or painted blue and shall be marked with an International Symbol of Accessibility complying with Section 11B-703.7.2.1 International Symbol of Accessibility a minimum 36 inches wide by 36 inches high in white or a suitable contrasting color. The centerline of the International Symbol of Accessibility shall be a maximum of 6 inches from the centerline of the parking space, its sides parallel to the length of the parking space and its lower corner at, or lower side aligned with, the end of the parking space. §11B-502.6.4.2 ☐ An additional sign shall be posted either; 1) in a conspicuous place at each entrance to an off-street parking facility or 2) immediately adjacent to on-site accessible parking and visible from each parking space. §11B-502.8 ☐ The additional sign shall not be less than 17 inches wide by 22 inches high. §11B-502.8.1 ☐ The additional sign shall clearly state in letters with a minimum height of 1 inch the following: §11B-502.8.2 "Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or special license plates issued for persons with disabilities will be towed away at the owner’s expense. Towed vehicles may be reclaimedby telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a. ☐ Signs intended for use by pedestrians within parking facilities, including directional or informational signsindicating parking sections or levels, shall comply with the requirements of Section 11B-216. §11B-216.5.2 Sheet A.1Show exit signage location.Show travel egress distance from the most remote location to the exterior exit doorway.Provide an enlarged restroom floorplan for accessibility requirements.See checklist below for accessibility requirements. TOILET AND BATHING ROOM CLEARANCES Item # Sheet # Corrections Requested Respond ☐ Where toilet facilities and bathing facilities are provided, they shall comply with 11B-213 Toilet Facilities and Bathing Facilities. Where toilet facilities and bathing facilities are provided in facilities permitted by 11B-206.2.3 Multi-Story Buildings and Facilities Exceptions1 and 2 not to connect stories by an accessible route, toilet facilities and bathing facilities shall be provided ona story connected by an accessible route to an accessible entrance. §11B-213.1 ☐ Where separate toilet facilities are provided for the exclusive use of separate user groups, the toilet facilities serving each user group shall comply with11B-213 Toilet Facilities and Bathing Facilities. §11B-213.1.1 ☐ Where toilet rooms are provided, each toilet room shall comply with 11B-603 Toilet and Bathing Rooms. Where bathing rooms are provided, each bathing room shall comply with 11B-603 Toilet and Bathing Rooms. §11B-213.2 (See exception) ☐ Unisex toilet rooms shall contain not more than one lavatory, and not more than two water closets without urinals or one water closet and one urinal. Unisex bathing rooms shall contain one shower or one shower and one bathtub, one lavatory, and one water closet. Doors to unisex toilet rooms and unisex bathing rooms shall have privacy latches. §11B-213.2.1 ☐ Door shall not swing into the clear floor space or clearance required for any fixture. Other than the door to the accessible water closet compartment, a door in any position may encroach into the turning space by 12 inches maximum. §11B-603.2.3 ☐ At single user toilet or bathing rooms, doors shall be permitted to swing into the clear floor space or clearance required for any fixture only if a 30 inch by48-inch minimum clear floor space is provided within the room beyond the arc of the door swing. §11B-603.2.3 (See exception) ☐ Mirrors located above the lavatories or countertops shall be installed within the bottom edge of the reflecting surface 40 inches maximum above the finish floor or ground. Mirrors not located above the lavatories or countertops shall be installed with the bottom edge of the reflecting surface 35 inches maximum above the finish floor or ground. §11B-603.3 ☐ Coat hooks shall be located within one of the reach ranges specified in Section 11B-308. Shelves shall be located 40 inches minimum and 48 inches maximum above the finish floor. Medicine cabinets shall be located with a usable shelf no higher than 44 inches maximum above the finish floor. §11B-603.4 ☐ Where towel or sanitary napkin dispensers, waste receptacles, or other accessories are provided in toilet facilities, at least one of each type shall be located on an accessible route. All operable parts, including coin slots, shall be 40 inches maximum above the finish floor. Baby changing stations are not required to comply with Section 11B-603.5 (See exception) §11B-603.5 ☐ Bathtubs shall comply with section 11B-607 including the requirements for clearances, grab bars, seats, controls, shower-spray unit and water and bathtub enclosures. ☐ Shower compartments shall comply with section 11B-608 including the requirements for clearances, grab bars, seats, controls, shower spray unit and water,thresholds, shower enclosures, shower floor or ground surface and soap dish. SIGNS RELATED TO TOILETS AND BATHRING FACILITIES Item # Sheet # Corrections Requested Respond ☐ Entrances leading to toilet rooms and bathing rooms complying with 11B-603 Toilet and Bathing Rooms shall be identified by a geometric symbol complying with 11B-703.7.2.6 Toilet and Bathing Room Geometric Symbols. Where existing toilet rooms or bathing rooms do not comply with 11B-603 Toilet and Bathing Rooms, directional signs indicating the location of the nearest compliant toilet room or bathing room within the facility shall be provided. Signs shall comply with 11B-703.5 Visual Characters and shall include the International Symbol of Accessibility complying with11B-703.7.2.1 ISA. Where existing toilet rooms orbathing rooms do not comply with 11B-603 Toilet and Bathing Rooms, the toilet rooms or bathing rooms complying with 11B-603 Toilet and Bathing Rooms shall be identified by the International Symbol of Accessibility complying with 11B-703.7.2.1 ISA. Where clustered single user toilet rooms or bathing facilities are permitted to use exceptions to 11B-213.2 Toilet and Bathing Rooms, toilet rooms or bathing facilities complying with 11B-603 Toilet and Bathing Rooms shall be identified by the International Symbol of Accessibility complying with 11B-703.7.2.1 ISA unless all toilet rooms and bathing facilities comply with 11B-603 Toilet and Bathing Rooms. Existing buildings thathave been remodeled to provide specific toilet rooms or bathing rooms for public use that comply with thesebuilding standards shall have the location of and thedirections to these rooms posted in or near the buildinglobby or entrance on a sign complying with 11B-703.5Visual Characters, including the International Symbol ofAccessibility complying with 11B-703.7.2.1 ISA. §11B-216.8 ☐ Pictograms shall comply with the following: ☐ Pictograms shall have a field height of 6 inches minimum. Characters and Braille shall not be located in the pictogram field. §11B-703.6.1 ☐ Pictograms and their field shall have a non-glare finish. Pictograms shall contrast with their field with either a light pictogram on a dark field or a dark pictogram on a light field. §11B-703.6.2 ☐ Pictograms shall have text descriptors located directly below the pictogram field. Text descriptors shall comply with 11B-703.2 Raised Characters,11B-703.3 Braille and 11B-703.4 Installation Heightand Location. §11B-703.6.3 ☐ The installation height and location of Pictogram signs shall be per §11B-703.4.1. ☐ Symbols shall comply with the following: ☐ Doorways leading to toilet rooms and bathing rooms shall be identified by a geometric symbol complying with 11B-703.7.2.6 Toilet and Bathing Facilities Geometric Symbols. The symbol shall be mounted at 58 inches minimum and 60 inches maximum above the finish floor or ground surface measured from the centerline of the symbol. Where a door is provided the symbol shall be mounted within 1 inch of the vertical centerline of the door. §11B-703.7.2.6 (See exception) ☐ Men’s toilet and bathing facilities shall be identified by an equilateral triangle, ¼ inch thick with edges 12 inches long and a vertex pointing upward. The triangle symbol shall contrast with the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.1 ☐ Women’s toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.2 ☐ Unisex toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter with a ¼ inch thick triangle with a vertex pointing upward superimposed on the circle and within the 12-inch diameter. The triangle symbol shall contrast with the circle symbol, either light on a dark background or dark on a light background. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background.§11B-703.7.2.6.3 Sheet A.2Detail 2: Show structural connection between top of bracing to roof framing. Sheet S-1Provide reference for structural connection between the mechanical unit and roof framing.