HomeMy WebLinkAbout248341_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10198422 through 10198426 PROJECT ADDRESS: 1221,1231, 1241, 1251, 1261 E Dyer Rd PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/10/2018 INITIAL REVIEW 12/19/2018 EXPIRATION 6/8/2019 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Danny Travis 3. TEL: (323)200-2663 FAX: VALUATION:$1,200,000 EMAIL: Dtravis@rchstudios.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.Sheet T-1.02, please update the code section to 2016 CBC.Sheets A-2.03 & A-2.04, provide missing details or reference sheet. See the red marks on these sheets of drawings.Sheets A-4.01 & S3-00, provide a typical section at the bottom of the proposed elevations and show the clearance between the wood louvers & ground surface. Show compliance with CBC Section 2304.12.1.5.Sheet S1-00, under the “Design Criteria” , please update the code reference to 2016 California Building Code (CBC).Sheet S2-02, provide missing beam sizes as marked on the drawings. Sheet s2-03, footing (N)F3 to be added to the footing schedule.All drawings and supporting documents shall be prepared, stamped and signed by a California licensed architect or registered civil engineer.The structural sheets are not signed at this time.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceIt is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards.Seems like this site has been updated in past to comply with the accessibility requirements and REFERENCE SHEETS are submitted for this purpose. Please confirm this statement on the drawings.See other red marks on the drawings. Please resubmit the marked up set with revised drawings for recheck.