HomeMy WebLinkAbout247658_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10198221
PROJECT ADDRESS:
610 S Newhope St Unit# A
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/10/2018
INITIAL REVIEW
4/1/2019
EXPIRATION
6/8/2019
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Steven Jones
3.
TEL:
(714)636-9800
FAX:
(714)636-9900
VALUATION: $180,363.00
EMAIL:
steve@olympiacorp.net
FLOOD ZONE: X-0602320256J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2016 California Residential Code (CRC); 2016 California Building Code (CBC); CMC = 2016 California Mechanical Code; CPC = 2016California Plumbing Code; CEC = 2016 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.
Please these comments apply to plan file numbers 10198221 to 10198229.
Bedrooms need to have egress windows. Please identify the windows that complies with the egress requirements, and specify the actual clear dimension of the openings and its height above ground.
Provide a 1-hour construction details for all garages located on the property line. Cross reference details with the plans.
Show on floor plan the requirement for an EV ready panel and raceway.
Show on plans the requirements for solar ready.
The window above the stair landing might have to be tempered glass based on its elevation above the landing.
List the green building sheets on the index.
Add notes to plan to show the EV ready and the raceways for solar ready.
Is the perimeter wall part of this permit?
Provide detail of the stair handrail.
Provide a soil’s report for this project.