HomeMy WebLinkAbout245680_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10197661 PROJECT ADDRESS: 600 W Warner Ave PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, F-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 9/11/2018 INITIAL REVIEW 11/6/2018 EXPIRATION 3/10/2019 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Robert Rieck 3. TEL: (714)668-9199 FAX: VALUATION:$72,000.00 EMAIL: Billing@royalmfgind.com FLOOD ZONE:X-0602320259J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039)Please clarify if the system is a ballast system, or attached to the roof structure? It seems there are details for both.If the system is a ballast system, the weight of the ballast should be included in the weight calculations.Please make sure the engineer of record sign the sheet with the weight calculations.The scale shown for the plan is 1/16”=1’ or 1”=16’. The dimension do not match the scale.Is the roof flat?Per section 3111.2.3, if the building is greater than 250 in any dimension, the perimeter access need to be 6ft. not 4 ft.Based on the scale shown the building is wider than 250 ft.Please provide dimensions.Provide a minimum 4 ft pathway. (dimension the pathway way shown between the arrays to be a min. of 4ft.Identify all skylights and show complianc3e with the smoke ventilation of section 3111.2.3.3