HomeMy WebLinkAbout256143_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101100830
PROJECT ADDRESS:
1901 E Alton Ave Unit# 150
PLAN CHECK ENGINEER:
Heidari, FredTEL:714
647-5862
EMAIL:
fHeidari@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
7/22/2019
INITIAL REVIEW
7/31/2019
EXPIRATION
1/18/2020
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Richard Martin
3.
TEL:
(949)851-3044
FAX:
VALUATION: $1,100,000.00
EMAIL:
beck-martin@sbcglobal.net
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceExiting from any occupied point in a building or structure on the subject site must be continuous, unobstructed, and undiminished to a public way. Provide a floor plan for the existing second floor and show the traveling distance for 2 exits of the second floor. Revise drawings to show compliance.Due to Demo work, the existing stair near the station 1107 is left with no defined path to the exterior of the building. Per CBC Section 1003.6: “THE PATH OF EGRESS TRAVELALONG A MEANS OF EGRESS SHALL NOT BE INTERUPPTED BY A BUILDING ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENET…” Please revise the drawings to show compliance.Provide completely dimensioned floor plans, elevations and sections of existing sanitary facility insuring wheelchair clearances complying with CBC Section 11B-604 and the California Plumbing Code.Drinking fountains serving the area of new work shall be accessible. Revise drawings to show compliance.See other red marks on the drawings. Please resubmit the marked up set with revised plans for recheck.