HomeMy WebLinkAbout255198_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101100519 PROJECT ADDRESS: 2702 S Shannon St PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/20/2019 INITIAL REVIEW 6/30/2019 EXPIRATION 12/17/2019 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Cara Smith 3. TEL: (714)401-5870 FAX: VALUATION:$242,250.00 EMAIL: cara@wecann.biz FLOOD ZONE:X-0602320258JINSTRUCTIONS FOR PROCEEDING WITH THE PLAN CHECK (PC) PROCESS: Review corrections on this Plan Check Correction Sheets, on the plans, and calculations. For any questions related to these PC corrections, email or call the Plan Check Engineer. See contact information above. Provide a written response or reference to details pursuant to the corrections. Any revisions on the plans shall be identified as part of your responses. Submit the original checked set of plans and calculations, three corrected set of plans, two corrected set of structural calculations, and this plan-check correction sheets to the Building Department. Unprepared responses with incomplete plans or calculations will delay plan check process. Once all the items have been corrected to comply with the code requirements and clearances are obtained, the building permit will be ready to be issue.IMPORTANT ITEMS TO READ: Your early attention is suggested to the approval process from other Departments as listed in the Plan Check Checklist due to possible delays resulting from a public hearing or other processes required by other Departments. The Planning Department, Public Works Agency, Police Department, Orange County Fire Agency, and others may have requirements that could significantly affect the final design of the project. The permit application will expire 12 months from the plans submittal date. This review does not include mechanical, electrical, plumbing work (MEP). Separate applications, fees, and permits are required for MEP work. Please be advised that the permit will be issued upon verification of compliance with the corrections included herein. The approval of plans does not permit the violation of any section of the Building Code, or other ordinance or state law. Numbers in parenthesis refer to particular code sections of the 2016 edition of the California Building Code (CBC). ADMINISTRATION: Obtain all clearancesfromthe following departments listed below. It is necessary to apply immediately for the signoff as it can take months for some departments to review the project. Comply with all conditions given during approval prior to building permit issuance. ☒PlanningDivision approval on the final set of drawings (714-647-5804). Applicant is responsible to ensure the final set of drawings are stamped by the Planning Division. ☒Public WorksDepartment’s approval (714-647-5690) if project valuation exceeds $30,000, or has added plumbing fixtures, or added bedrooms, or exceeds 500 square foot. ☐ Grading Permit - Application is made through the Building Safety Division (714-647-5800) and the plan review is by the Public Works Agency (714-647-5690). ☒ Police Department approval on the final set of drawings. (647-5840). ☒Fire Department approval on the final set of drawings (714-647-5839) ☐School District Compliance Certificate; and a copy of the building permit application, signed by the plan reviewer, shall be required by the School District to verified the scope of work. The building permit must be signed by the property owner or licensed contractor or authorized agent at the time the building permit is issued: For owner-builder permits: Owner’s signature can be verified with owner’s driver license or other forms of valid ID. Owner’s representative must present owner’s approval with a copy of driver license or other forms of valid ID from the owner. For contractor building permits: Prior to the issuance of a building permit, the contractor shall have the following: Letter of authorization for agents. Certificate of workers Compensation Insurance made out to the Contractors State License Board. Copy of Contractor’s State License or pocket ID. Copy of City of Santa Ana business tax registration certificate or a newly paid receipt. Two sets of plans will be required during building permit issuance. Plans must be: Quality blue or black line drawings with uniform and light background color. Maximum 36” x 48” size with minimum 1/8” lettering size. Minimum 18” x 24” size with minimum 1/8” lettering size. Sticky back details must produce prints without contrasting shades of background color. For new buildings and additions, one additional copy of only architectural set is required for the County Tax Assessor. (California Revenue and Taxation Section 72). Applicant is responsible to ensure the final set of plans are stamped by: ☒ Planning Department ☒ Building Department ☒ Police Department ☒ Orange County Fire Authority PLAN REVIEW COMMENTS Title Sheet Revise building address to “2702 S. Shannon St.” under Project Data. Project Scope indicates existing wall to be removed per plan. Provide wall legend or keynote on sheet A101 and clearly identify which existing walls to be removed. Project Scope indicates addition of door per plan. Identify all new doors and existing doors on sheet A102. Project Scope indicates new non-bearing wall per plan. Identify new wall location and provide detailed construction of such wall. Structural sheet shows wall legend with 4-inches wood stud at maximum height of 13 feet. However, the location of these walls are not shown on the architectural floor plan. On sheet A102 from grid line 2 to grid line 6, portion of the building is shown as N.I.C. (Not in Scope). Revise all floor plan for consistency. Under Project Data, revise code reference from “2010 ADA” to “2016 California Building Code Chapter 11B”. See attached handout for “Information Required for Commercial Cannabis Business Mechanical Plan Check” CCB. Under Project Data, occupancies are shown as “B/F1/S”. Identify all occupancies location on the floor plan. Under Project Data, specify the proposed tenant improvement floor area. Floor area for the entire building is shown. However, floor area for the portion of tenant improvement is missing. Sheet G002 Notes on sheet G002 are based on code reference 2017 edition of Los Angeles Building Code. City of Santa Ana adapts the 2016 California Building Code with local city ordinances. Remove all Los Angeles code references as necessary. Sheet A100 See the following checklist for accessible van parking space requirements. PARKING SPACES Item # Corrections Requested Respond ☐ Where parking spaces are provided, accessible parking spaces shall be provided in number and kind required per Section 11B-208 Parking Spaces. §11B-208.1 ☐ Provide ( ) accessible parking spaces as required by Table 11B-208.2. §11B-208.2 (See exceptions) ☐ Provide accessible spaces for each parking facility (parking lots and parking structures). The number of parking spaces required to be accessible is to be calculated separately for each parking facility; the required number is not based on the total number of parking spaces provided in all of the parking facilities provided on site. §11B-208 ☐ Ten percent of patient and visitor parking spaces provided to serve hospital outpatient facilities, and free- standing buildings providing outpatient clinical services of a hospital, shall comply with Section 11B-502 Parking Spaces. §11B-208.2.1 ☐ Twenty percent of patient and visitor parking spaces provided to serve rehabilitation facilities specializing in treating conditions that affect mobility and outpatient physical therapy facilities shall comply with Section 11B-502 Parking Spaces. §11B-208.2.2 ☐ X One in every six or fraction of six parking spaces required by Section 11B-208.2 Minimum Number, but not less than one, shall be served by an access aisle 96 inches wide minimum placed on the side opposite the driver’s side when the vehicle is going forward into the parking space and shall be designated “van accessible”. All such spaces may be grouped on one Level of a parking structure. §11B-208.2.4, 11B-502, Fig 11B-502, 11B-502.3, & 11B-502.3.3 ☐ Accessible parking spaces complying with Section 11B- 502 Parking Spaces serving a particular building or facility shall be located on the shortest accessible route of travel from adjacent parking to an accessible Entrance (as near as practical to an accessible entrance). §11B-208.3.1 ☐ In buildings with multiple accessible entrances with adjacent parking, accessible parking spaces complying with Section 11B-502 Parking Spaces shall be dispersed and located closest to the accessible entrances. §11B-208.3.1 ☐ In parking facilities that do not serve a particular building or facility, accessible parking spaces complying with Section 11B-502 Parking Spaces shall be located on the shortest accessible route of travel to an accessible pedestrian entrance of the parking facility. §11B-208.3.1 ☐ X Dimension minimum 18-foot long car and van accessible parking space(s) and access aisle(s). §11B-502.2, Figures 11B-502.2 and 11B-502.3 ☐ Dimension minimum 9-foot width at accessible car parking space. §11B-502.2, Fig. 11B-502.2 & Fig.11B-502.3 ☐ X Dimension minimum 12-foot wide accessible van parking space with minimum 5-foot wide access aisle. Van parking spaces shall be permitted to be minimum 9 feet wide where access aisle is 8-foot wide minimum. §11B-502.2, Figures 11B-502.2 and 11B-502.3 ☐ Car and van stall access aisle shall be 5 foot wide minimum and shall adjoin an accessible route. Two parking spaces shall be permitted to share a common access aisle. §11B-502.3, Figures 11B-502.2 and 11B-502.3 ☐ X Access aisles shall be marked with a blue painted borderline around their perimeter. The area within the blue borderlines shall be marked with hatched lines a maximum of 36 inches on center in a color contrasting with that of the aisle surface, preferably blue or white. The words "NO PARKING" shall be painted on the surface within each access aisle in white letters a minimum of 12 inches in height and located to be visible from the adjacent vehicular way. Access aisle markings may extend beyond the minimum required length. §11B-502.3.3, Figure 11B-502.3.3 ☐ Access aisles shall not overlap the vehicular way. Access aisles shall be permitted to be placed on either side of the parking space except for van parking spaces which shall have access aisles located on the passenger side of the parking spaces. §11B-502.3.4 ☐ Clearly show minimum vertical clearance of 8 feet 2 inches at accessible parking spaces and along at least one vehicle access route to such spaces from site entrances and exits. §11B-502.5 ☐ X Parking space identification signs shall include the International Symbol of Accessibility complying with Section11B-703.7.2.1 International Symbol of Accessibility. §11B-502.6, Figure 11B-703.7.2.1 ☐ X Signs identifying van parking spaces shall contain additional language or an additional sign with the designation “van accessible.” Signs shall be 60 inches minimum above the finish floor or ground surface measured to the bottom of the sign. §11B-502.6 ☐ X Parking identification signs shall be reflectorized with a minimum area of 70 square inches. §11B-502.6.1 ☐ X Additional language or an additional sign below the International Symbol of Accessibility shall state “Minimum Fine $250.” §11B-502.6.2 ☐ X A parking space identification sign shall be visible from each parking space. Signs shall be permanently posted either immediately adjacent to the parking space or within the projected parking space width at the head end of the parking space. Signs may also be permanently posted on a wall at the interior end of the parking space. §11B-502.6.3 ☐ X Each accessible car and van space shall have surface identification complying with either of the following schemes: §11B-502.6.4 ☐ The parking space shall be marked with an International Symbol of Accessibility complying with Section 11B-703.7.2.1 International Symbol of Accessibility in white on a blue background a minimum 36 inches wide by 36 inches high. The centerline of the International Symbol of Accessibility shall be a maximum of 6 inches from the centerline of the parking space, its sides parallel to the length of the parking space and its lower corner at, or lower side aligned with, the end of the parking space length. §11B-502.6.4.1 ☐ The parking space shall be outlined or painted blue and shall be marked with an International Symbol of Accessibility complying with Section 11B-703.7.2.1 International Symbol of Accessibility a minimum 36 inches wide by 36 inches high in white or a suitable contrasting color. The centerline of the International Symbol of Accessibility shall be a maximum of 6 inches from the centerline of the parking space, its sides parallel to the length of the parking space and its lower corner at, or lower side aligned with, the end of the parking space. §11B-502.6.4.2 ☐ X An additional sign shall be posted either; 1) in a conspicuous place at each entrance to an off-street parking facility or 2) immediately adjacent to on-site accessible parking and visible from each parking space. §11B-502.8 ☐ The additional sign shall not be less than 17 inches wide by 22 inches high. §11B-502.8.1 ☐ The additional sign shall clearly state in letters with a minimum height of 1 inch the following: §11B-502.8.2 "Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or special license plates issued for persons with disabilities will be towed away at the owner’s expense. Towed vehicles may be reclaimed by telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a. ☐ Signs intended for use by pedestrians within parking facilities, including directional or informational signs indicating parking sections or levels, shall comply with the requirements of Section 11B-216. §11B-216.5.2 Parking spaces and access aisles shall be designed so that persons using them are not required to travel behind parking spaces other than to pass behind the parking space in which they parked. §11B-502.7.1 Revise the correct detail-referencing number on accessible parking. Detail 4 on sheet A500 does not match the parking-space layout on site plan. Accessible Path of Travel is shown from the Public Right-of-Way. However, there is no sidewalk on existing condition and the path is through a vehicular way. Provide a code compliant Path of Travel design. Show all property lines on site plan. It appears the building is located on a zero lot-line. The propose design directs one exit to adjacent property which is not permitted by building code. Sheet A101 Provide keynotes for elements to be demolished. Sheet A102 Provide wall legend and details for wall along grid line 2. What is the fire-resistive rating for wall along grid line 2 if any? Demolition floor plan shows a door is being removed along grid line 2 near grid line G. Provide a wall in-fill detail. Show Path of Travel from the Entrance to area of tenant improvement. Show travel distance to the exit door. Will there be cannabis manufacturing, retail, or extracting use at the remaining portion of the building? See the following checklist for accessible restroom requirements. Single-Accommodation Toilet Room Single-accommodation toilet room shall be accessible. Provide the following: ☐Enlarged toilet-room floor plan. ☐Toilet-room elevation drawings. ☐Accessible details. ☐Geometric-symbol detail on the toilet-room door. Geometric Symbol Identify the geometric symbol location: ☐On elevation drawing, show geometric symbol at toilet-room entrance. (11B-703.7.2.6) ☐Specify Men’s toilet geometric symbol at toilet-room entrance. (11B-703.7.2.6.1) ☐Specify Women’s toilet geometric symbol at toilet-room entrance. (11B-703.7.2.6.2) ☐Specify Unisex toilet geometric symbol at toilet-room entrance. (11B-703.7.2.6.3) Specify the position of geometric symbol: ☐On elevation drawing, provide dimension line on the center of geometric symbol measured at 58-inches minimum and 60-inches maximum above finished floor. Dimensional range implies construction tolerance beyond specified limits is not permitted. (11B-703.7.2.6) ☐On elevation drawing, show a one-inch maximum dimension-line between the centerline of geometric symbol and vertical centerline of the door. (11B-703.7.2.6) Provide note on geometric symbols:” edges shall be eased or rounded at 1/16-inch minimum, or chamfered at 1/8-inch maximum. Vertices shall be radius between 1/8-inch minimum and ¼-inch maximum.” Provide Men’s toilet geometric symbol detail: ☐Men’s Toilet geometric symbol shall be an equilateral triangle, ¼-inch thick with edges 12-inches long and a vertex pointing upward. (11B-703.7.2.6.1) ☐Specify contrast requirement between the triangle symbol and the door, either light on a dark background or dark on a light background. (11B-703.7.2.6.1) Provide Women’s toilet geometric symbol detail: ☐Provide Women’s Toilet geometric symbol detail. Women’s Toilet geometric symbol shall be a circle, ¼-inch thick and 12-inches in diameter. (11B-703.7.2.6.2) ☐Specify contrast requirement between the circle symbol and the door, either light on a dark background or dark on a light background. (11B-703.7.2.6.2) Provide Unisex toilet geometric symbol detail: ☐Provide Unisex Toilet geometric symbol detail. Unisex Toilet geometric symbol shall be a circle, ¼-inch thick and 12-inches in diameter with a ¼-inch thick triangle with a vertex pointing upward, superimposed on and geometrically inscribed within the circle and within the 12-inch diameter. The vertices of the triangle shall be located ¼-inch maximum from the edge of the circle. (11B-703.7.2.6.3) ☐Specify contrast requirement between the triangle symbol and the circle symbol, either light on a dark background or dark on a light background. (11B-703.7.2.6.3) ☐Specify contrast requirement between the circle symbol and the door, either light on a dark background or dark on a light background. (11B-703.7.2.6.3) Toilet Sign Specify installation height of the toilet sign: ☐Specify 60-inches maximum from the baseline of highest line of raised characters to the finished floor. The maximum dimension implies construction tolerance is not permitted. (11B-703.4.1) ☐Specify 48-inches minimum from the baseline of lowest braille cells to the finished floor. The minimum dimension implies construction tolerance is not permitted. (11B-703.4.1) Specify location of the toilet sign: ☐The toilet-sign shall be located at latch side of the door. (11B-703.4.2) ☐Where there is no wall space at latch side of the door, provide toilet-sign on nearest adjacent wall. §11B-703.4.2 ☐Provide a clear floor-space of 18 inches minimum by 18 inches minimum, centered on tactile characters beyond the arc of door swing. (11B-703.4.2) Specify Braille position on the toilet sign: ☐Revise toilet-sign detail to show braille position below the corresponding text in a horizontal format, flush left or centered. (11B-703.3.2) ☐Show braille position below the entire text on a multi-lined toilet sign. (11B-703.3.2) ☐Provide dimension line to show distance between braille and tactile characters 3/8-inch minimum and ½-inch maximum. Dimensional range implies construction tolerance beyond specified limits is not permitted. (11B-703.3.2) ☐Provide dimension line to show distance between braille and raised borders at 3/8-inch minimum. The minimum dimension implies construction tolerance is not permitted. (11B-703.3.2) Provide Braille notes on the toilet sign: ☐Braille shall be contracted (Grade 2). (11B-703.3) ☐Braille dots shall have a domed or rounded shape. (11B-703.3.1) ☐The indication of an uppercase letter or letters shall only be used before the first word of sentences, proper nouns and names, individual letters of the alphabet, initials, and acronyms. (11B-703.3.1) Pictogram Provide the following on pictogram detail: ☐Dimensional line 6-inches minimum on pictogram field-height. (11B-703.6.1) ☐Characters and braille shall not be located in the pictogram field. (11B-703.6.1) ☐Text descriptors located directly below the pictogram field. (11B-703.6.3) Provide notes on pictograms: ☐Pictograms and their field shall have a non-glare finish. (11B-703.6.2) ☐Pictograms shall contrast with their field with either a light pictogram on a dark field or a dark pictogram on a light field. (11B-703.6.2) Floor clearances in toilet room Show the following clearance on toilet-room floor plan: ☐A minimum of 60-inch diameter turning-space within the room. The minimum dimension implies construction tolerance is not permitted. (11B-603.2.1) ☐A clear floor-space (30” min. wide x 48” min. deep) within toilet room beyond the arc of door swing. (11B-603.2.3 Exception 2) ☐Clearance around water closet 60-inches minimum measured perpendicular from the side wall and 56-inches minimum measured perpendicular from the rear wall. The minimum dimension implies construction tolerance is not permitted. (11B-604.3.1) ☐Maneuvering space 60-inches minimum wide and 48-inches minimum deep in front of the water closet. The minimum dimension implies construction tolerance is not permitted. (11B-604.3.1) ☐A clear-floor space (30” min. wide x 48” min. deep) positioned for a forward approach in front of the lavatory. (11B-606.2) Water closet Specify position and height of the water closet: ☐The water closet shall be positioned with a wall or partition to the rear and to one side. (11B-604.2) ☐The water closet shall be arranged for a left-hand or right-hand approach. (11B-604.2) ☐Specify 17-inches minimum and 18-inches maximum dimensional range between side wall and centerline of water closet. Dimensional range implies construction tolerance beyond specified limits is not permitted. (11B-604.2) Specify dimensional limits and notes on toilet seat: ☐Toilet seat above finished floor shall be 17-inches minimum and 19-inches maximum measured to top of the seat. Dimensional range implies construction tolerance beyond specified limits is not permitted. (11B-604.4) ☐Provide note: “Seat shall not be sprung to return to a lifted position.” (11B-604.4) ☐Provide note: “Seat shall be 2 inches high maximum.” (11B-604.4) ☐Provide note: “A 3-inch high seat shall be permitted only in alterations where the existing fixture is less than 15 inches high.” (11B-604.4) Specify dimensional limit and notes on water-closet flush control: ☐On the water-closet elevation drawing, specify the hand-operated flush-controls shall be located 44-inches maximum above the floor. The maximum dimension implies construction tolerance is not permitted. (11B-604.6) ☐Provide note: “Flush controls shall be located on the open side of the water closet” (11B-604.6) ☐Provide note: “Flush control shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate flush control shall be 5-pounds maximum.” (11B-309.4 & §11B-604.6) Grab bars Provide grab bars on the side-wall closest to the water closet. (11B-604.5) Provide dimensional lines on the side-wall grab bar.The minimum and maximum dimension implies construction tolerance is not permitted. (11B-604.5.1) ☐42-inches minimum in length. ☐12-inches maximum from the rear wall. ☐54-inches minimum from the rear wall. ☐24-inches minimum in front of the water closet. ☐Installed in a horizontal position, 33-inches minimum and 36-inches maximum above the finished floor measured to the top of gripping surface. (11B-609.4) Provide grab bars on the rear-wall closest to the water closet. (11B-604.5) Provide dimensional lines on the rear-wall grab bar. The minimum and maximum dimension implies construction tolerance is not permitted. (11B-604.5.2) ☐36-inches minimum in length. ☐Extends from centerline of the water closet 12-inches minimum on one side and 24-inches minimum on the other side. ☐Installed in a horizontal position, 33-inches minimum and 36-inches maximum above the finished floor measured to the top of gripping surface. (11B-609.4) Provide grab-bars cross section detail. The minimum and maximum dimension implies construction tolerance is not permitted. (11B-609.2.1) ☐Circular cross-sections shall have an outside diameter of 1.25-inches minimum and 2-inches maximum. ☐Non-circular cross-sections shall have a cross section dimension of 2-inches maximum and a perimeter dimension of 4-inches minimum and 4.8-inches maximum. Provide grab-bar spacing details. The minimum and maximum dimension implies construction tolerance is not permitted. (11B-609.3): ☐The space between the wall and the grab bar shall be 1.5 inches. Please note this is an absolute dimension, not minimum. ☐The space between grab bar and projecting objects shall be 1.5 inches minimum. ☐The space between grab bar and at the ends shall be 1.5 inches minimum. ☐The space between grab bar and projecting objects above shall be 12 inches minimum. Provide notes on grab bar: ☐Grab bars and any wall or other surfaces adjacent to grab bars shall be free of sharp or abrasive elements and shall have rounded edges. (11B-609.5) ☐Grab bars shall not rotate within their fittings. (11B-609.6) Allowable stresses shall not be exceeded for material used when a vertical or horizontal force of 250 pounds is applied at any point on the grab bar, fastener, mounting device, or supporting structure. Provide a structural connection detail between the grab bar and supporting structure. Specify the type of fastener and minimum embedment length into the supporting structure. (11B-609.8) Toilet Paper Dispensers Specify position of toilet-paper dispensers by providing dimensional lines on elevation drawing. The minimum and maximum dimension implies construction tolerance is not permitted. (11B-604.7): ☐7-inches minimum in front of water closet measured to the centerline of the dispenser. ☐9-inches maximum in front of water closet measured to the centerline of the dispenser. ☐The outlet of toilet-paper dispenser is 19-inches minimum above the finished floor. ☐The outlet of toilet-paper dispenser below the grab bar. Provide note on toilet-paper dispensers: “The toilet-paper dispenser shall be the type that allows for continuous paper flow and does not control delivery.” (11B-604.7) Lavatory Specify position and height on lavatory by providing dimensional lines. Specify the following dimensions on elevation drawing. §11B-606.2 ☐18 inches minimum from center line of lavatory to adjacent wall. ☐Higher-front rim at 34-inches maximum above the finished floor. Provide knee-and-toe clearance detail underneath the lavatory.Specify the following dimensions on elevation drawing. The minimum and maximum dimension implies construction tolerance is not permitted. (11B-606.2): Knee clearance is the spacebetween 9-inches and 29-inches above finished floor: ☐29-inches minimum above finished floor at front-end of lavatory. ☐27-inches minimum above finished floor at 8-inches deep. ☐At 9-inches above finished floor, extend 11-inches minimum under the lavatory. ☐At 9-inches above finished floor, extend 25-inches maximum under the lavatory. ☐Knee clearance shall be 30-inches wide minimum. Toe clearanceis the space between finished floor and 9-inches above finished floor: ☐Extend 17-inches minimum under the lavatory. ☐Extend 19-inches maximum under the lavatory. ☐Toe clearance shall be 30-inches wide minimum. Lavatory Faucets Provide notes for lavatory faucets: (11B-308.1, 309.4, 606.4) ☐Hand-operated faucets shall remain open for 10 seconds minimum. ☐Controls for faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist. ☐The force required to activate operable parts is no greater than 5-pounds maximum. ☐Hand-operated controls for faucets shall be located within accessible reach ranges. Exposed Pipes Provide notes for exposed pipes: (11B-606.5) ☐Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. ☐There shall be no sharp or abrasive surfaces under lavatories. Mirrors Provide dimensional line on mirror located above lavatory with the bottom edge of reflective surface 40-inches maximum above the finished floor. The maximum dimension implies construction tolerance is not permitted. (11B-603.3) Accessories Provide dimensional lines on the following accessories. The minimum and maximum dimension implies construction tolerance is not permitted. (11B-603.3, 603.4, 603.5): ☐Mirror not located above lavatory with the bottom edge of reflective surface 35-inches maximum above the finished floor. ☐Coat hook 48-inches maximum above finished floor. ☐Shelves 40-inches minimum and 48-inches maximum above finished floor. ☐Sanitary-napkin dispenser 40-inches maximum above finished floor. ☐Waste receptacle 40-inches maximum above finished floor. ☐Soap dispenser 40-inches maximum above finished floor. Sheet A500 Provide design of roof screen. Sheet S1.0 The proposed new wood-stud wall is located in an area where it states Not in Scope (NIC) on architectural drawing sheet A102. Cross reference detail 2 on the floor plan. Provide structural details for roof screening design per detail 13 sheet A500.