HomeMy WebLinkAbout253575_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101100028
PROJECT ADDRESS:
3226 W Hood Ave
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/6/2019
INITIAL REVIEW
7/9/2019
EXPIRATION
12/3/2019
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Hung Le
3.
TEL:
(562)412-1818
FAX:
(562)868-2128
VALUATION: $15,524.00
EMAIL:
le_hung4946@yahoo.com
FLOOD ZONE: X-0602320256J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2016 California Residential Code (CRC); 2016 California Building Code (CBC); CMC = 2016 California Mechanical Code; CPC = 2016 California Plumbing Code; CEC = 2016 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
Provide dimension for the openings to show at least 65 % of the area below a minimum 6’-8” of each wall.
Show enclosed with any of the following;
a) insect screening
b) Approved translucent or transparent plastic not more than .125 inch in thickness.
C) Glass conforming to section R308.
Show ventilation is in compliance with AH103.2.
Provide double joists on line G for strap.
Provide dimension for post spacing.
Provide 2 # 4 rebar for new footings.
Provide detail at the ledger connection to show how shear integrity for the house will be maintained.
Provide complete engineering calculation for patio enclosure itself to show lateral resistance on line (B) and line (1) will be provided.