Loading...
HomeMy WebLinkAbout256358_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101100890 PROJECT ADDRESS: 901 W Civic Center Dr Unit# 340 PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862 EMAIL: fHeidari@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: II A, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/25/2019 INITIAL REVIEW 8/5/2019 EXPIRATION 1/21/2020 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Sean Nourani 3. TEL: (424)365-2070 FAX: (714)844-4371 VALUATION: $45,000.00 EMAIL: Seannourani@outlook.com FLOOD ZONE: X-0602320144J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceThe valuation of improvements for the subject building permit application has been calculated to be $150,000.00Occupant load is calculated as follows: - Office Area 100 SF/ Persons ( 2884 SF / 100 = 29 occupants) - Training Room 15 SF/ Persons (1014 SF / 15 = 67 occupants); 29+67 = 96 is the total occupant load of this space. - Please revise the total occupant load on the cover sheet of this drawing.Panic hardware (PH) shall comply with CBC Section 1010.1.10. Panic hardware shall be provided as required by above CBC Section: - An Occupancy with an occupant count > 50. Therefore, doors # 01, 12, & 13 shall be equipped with PHHand-activated door opening hardware shall be centered between 34” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Please update the notes on sheet “N-1.1”.CBC Section 1008.2.1, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Make a note on the drawings.