HomeMy WebLinkAbout259692_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
102102032
PROJECT ADDRESS:
604 S Ross St
PLAN CHECK ENGINEER:
Heidari, FredTEL:714
647-5862
EMAIL:
fHeidari@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/29/2019
INITIAL REVIEW
11/6/2019
EXPIRATION
4/26/2020
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Ruben Pena
3.
TEL:
(714)552-5731
FAX:
VALUATION: $5,000.00
EMAIL:
rpena@inkminded.com
FLOOD ZONE: X-0602320276J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTSResubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.This review does not include electrical work. Separate plan, application, fee, plan check, and permit may be required for electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide handrail details on the drawings showing compliance with CBC Section 1011.11, 1014.
- Handrails shall be 34 to 38” above the nosing of treads.
- Ends of handrails shall be returned or shall terminate in newel posts of safety terminals.
- Handrails projecting from a wall shall have a space of 1½” between the wall and the handrail.
- The handgrip potion of handrails shall not be less than 1¼” nor more than 2” cross-sectional dimension or
the shape shall provide an equivalent gripping surface. The handgrip portion of handrails shall have a smooth
surface with no sharp corners. Any wall or other surface adjacent to the handrail shall be free of sharp or
abrasive elements. Edges shall have a minimum radius of 1/8”.Handrails for stairways shall be adequate in strength and attachment in accordance with CBC Section 1607.8. The top of the guards at the top landing shall not be less than 42” in height.