HomeMy WebLinkAbout260975_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101102425
PROJECT ADDRESS:
1210 W Eighteenth St
PLAN CHECK ENGINEER:
Heidari, FredTEL:714
647-5862
EMAIL:
fHeidari@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/4/2019
INITIAL REVIEW
12/11/2019
EXPIRATION
6/1/2020
RECHECKS:
1. 01/02/2020
PROJECT APPLICANT CONTACT PERSON:
2.
Doug Risk
3.
TEL:
(714)234-9160
FAX:
VALUATION: $5,000.00
EMAIL:
coastalbuilders@signsdcglobal.net
FLOOD ZONE: X-0602320144J
A RECHECK OF YOUR DRAWINGS WAS COMPLETED TODAY, 01/02/2020; AND ITEMS # 10, 11, & 12 FROM THE PLAN CHECK LIST BELOW ARE NOT DONE/ COMPLETED AT THIS TIME.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.On the site plan, sheet “A-1”, there is a note for the patio cover in the back of this house to be demoed. It is not clear this patio cover will be demoed under a separate permit or under this permit. Please clarify. The structural calculation (the computer printout) does not show how the live & dealloads are calculated for beams # 1 & # 2. Provide a hand calculation to clearly show/ justify these loads.On the roof framing plan, show existing ceiling joist direction and their relationship with the proposed beams. Provide missing structural details as marked on sheet “S-2”. (ceiling joists shall be continuous to act as a tie for roof rafters).
Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Public Works Agency approval (647-5039).
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.In interior or exterior alterations, repairs, or additions requiring a permit and having a valuation in excess of $1,000, the entire dwelling shall be provided with smoke detectors located as required for a new dwelling. (CRC R314.3) Smoke alarms shall be installed in the following locations:
- In each sleeping room.
- Outside each separate sleeping area in the immediate vicinity of the bedrooms.In Interior or exterior alterations, repairs, or additions requiring a permit and having a valuation in excess of $1,000, an approved carbon monoxide alarm shall be installed in dwelling units and in sleeping units within which fuel-burning appliances are installed and in dwelling units that have attached garages shall be provided with carbon monoxide alarms (CRC R315)
- Carbon monoxide alarms shall only be required in the specific dwelling unit or sleeping unit for
which the permit was obtained. Carbon monoxide alarms required by Sections R315.1 and
R315.2 shall be installed in the following locations: ________.
- Outside of each separate dwelling unit sleeping area in the immediate vicinity of the bedroom(s).
- On every level of a dwelling unit including basements.
Exception:
Interconnection is not required in existing dwelling units where repairs do not result in the removal of wall and ceiling finishes, there is no access by means of attic, basement or crawl space, and no previous method for interconnection existed.