HomeMy WebLinkAbout261671_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101102629
PROJECT ADDRESS:
201 W Fourth St
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830
EMAIL:
aso@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/19/2019
INITIAL REVIEW
1/7/2020
EXPIRATION
6/16/2020
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Jeff Beddow
3.
TEL:
(949)722-7400
FAX:
(949)722-8855
VALUATION: $17,000.00
EMAIL:
jeff.saproperties@gmail.com
FLOOD ZONE: X-0602320276J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Please return marked up set of drawings with corrections.
Sheet A3
Detail 13: On elevation drawing, provide dimension line on the center of geometric symbol measured at 58 inches minimum and 60 inches maximum above finished floor. Dimensional range implies construction tolerance beyond specified limits is not permitted.§11B-703.7.2.6
Detail 9 & 10: On elevation drawing, show a one-inch maximum dimension-line between the centerline of geometric symbol and vertical centerline of the door. §11B-703.7.2.6
Detail 13: Provide note on geometric symbols:” edges shall be eased or rounded at 1/16 inch minimum, or chamfered at 1/8 inch maximum. Vertices shall be radius between 1/8 inch minimum and ¼ inch maximum.”
Men’s Toilet Geometric Symbol
Detail 13: Provide Men’s Toilet geometric symbol detail. Men’s Toilet geometric symbol shall be an equilateral triangle, 1/4 inch thick with edges 12 inches long and a vertex pointing upward. §11B-703.7.2.6.1
Detail 13:Specify contrast requirement between the triangle symbol and the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.1
Women’s Toilet Geometric Symbol
Detail 13: Provide Women’s Toilet geometric symbol detail. Women’s Toilet geometric symbol shall be a circle, 1/4 inch thickand 12 inches in diameter. §11B-703.7.2.6.2
Detail 13: Specify contrast requirement between the circle symbol and the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.2
Toilet Sign
Installation height and location
Restroom Floorplan: Show a clear floor-space of 18 inches minimum by 18 inches minimum, centered on tactile characters beyond the arc of door swing. §11B-703.4.2
Braille
Detail 14: Provide note on Braille:” Braille dots shall have a domed or rounded shape.” §11B-703.3.1
Detail 14: Provide note on Braille:” The indication of an uppercase letter or letters shall only be used before the first word of sentences, proper nouns and names, individual letters of the alphabet, initials, and acronyms.” §11B-703.3.1
Detail 14: Revise toilet-sign detail to show braille position below the corresponding text in a horizontal format, flush left or centered. §11B-703.3.2
Detail 14: Provide dimension line to show distance between braille and tactile characters 3/8 inch minimum and ½ inch maximum. Dimensional range implies construction tolerance beyond specified limits is not permitted.§11B-703.3.2
Detail 14: Provide dimension line to show distance between braille and raised borders at 3/8 inch minimum. The minimum dimension implies construction tolerance is not permitted.§11B-703.3.2
Pictogram
Detail 14: Provide dimension-line 6 inches minimum on pictogram field-height. §11B-703.6.1
Detail 14: Characters and braille shall not be located in the pictogram field. Revise detail. §11B-703.6.1
Detail 14: Provide note on pictograms:” Pictograms and their field shall have a non-glare finish.” §11B-703.6.2
WATER CLOSET
Position and Height
On the restroom floor plan or elevation drawing, specify 17 inches minimum and 18 inches maximum dimensional-range between side walland centerline of water closet. Dimensional range implies construction tolerance beyond specified limits is not permitted.§11B-604.2
Flush Control
Keynote 1: Provide note on water-closet hand-operated flush control: “Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. The force required to activate operable parts shall be 5 pounds maximum.” §11B-309.4 & §11B-604.6
Keynote 1: On the water-closet elevation drawing, specify the hand-operated flush-controls shall be located 44 inchesmaximum above the floor. The maximum dimension implies construction tolerance is not permitted. §11B-604.6
Seat
Provide note on toilet seat: “Seat shall not be sprung to return to a lifted position.” §11B-604.4
Provide note on toilet seat: “Seat shall be 2 inches high maximum.” §11B-604.4
Cross Section
Detail 12: Provide detail to demonstrate grab-bars with circular cross-sections shall have an outside diameter of 1.25 inches minimum and 2 inches maximum.Dimensional range implies construction tolerance beyond specified limits is not permitted.§11B-609.2.1
Surface Hazards
Provide note on grab bars: “Grab bars and any wall or other surfaces adjacent to grab bars shall be free of sharp or abrasive elements and shall have rounded edges.” §11B-609.5
Fittings
Provide note on grab bars: “Grab bars shall not rotate within their fittings.” §11B-609.6
Structural Strength
Allowable stresses shall not be exceeded for material used when a vertical or horizontal force of 250 pounds is applied at any point on the grab bar, fastener, mounting device, or supporting structure. Provide a structural connection detail between the grab bar and supporting structure. Specify the type of fastener and minimum embedment length into the supporting structure. §11B-609.8
Provide note on toilet-paper dispensers: “The toilet paper dispenser shall be the type that allows for continuous paper flow and does not control delivery.” §11B-604.7
LAVATORY
Position and Height
Restroom Floorplan: Provide dimension line to show 18 inches minimum from center line of lavatory to adjacent wall. The minimum dimension implies construction tolerance is not permitted. §11B-606.6
Knee and Toe Clearance
Provide detail to show Knee and Toe Clearance underneath the lavatory. Specify the following dimensions on elevation drawing. §11B-606.2
Knee clearance
Under the lavatory, space between 9 inches and 29 inches above finished floor shall be considered as knee clearance.§11B-306.3.1 Exception
Knee clearance at the front-end of the lavatory shall be 29 inches minimum above finished floor. §11B-306.3.3 Exception 1
Knee clearance underneath the lavatory at a depth of 8 inches shall be 27 inches minimum above finished floor. §11B-306.3.3 Exception 1
Knee clearance shall extend 25 inchesmaximum under the lavatory at 9 inches above finished floor. §11B-306.3.2
Knee clearance shall be 11 inches minimum deep at 9 inches above finished floor. §11B-306.3.3
Knee clearance shall be 30 inches wide minimum. §11B-306.3.5
Toe Clearance
Under the lavatory, space between finished floor and 9 inches above finished floor shall be considered as toe clearance. §11B-306.2.1
Toe clearance shall extend 17 inches minimum under lavatories. §11B-306.2.3
Toe clearance shall extend 19 inchesmaximum under lavatories. §11B-306.2.2 Exception
Toe clearance shall be 30 inches wide minimum. §11B-306.2.5
Faucets
Provide note on faucets: “Hand-operated metering faucets shall remain open for 10 seconds minimum.” §11B-606.4
Provide note on faucets: “Controls for faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.” §11B-309.4
Provide note on faucets: “The force required to activate operable parts is no greater than 5 pounds maximum.” §11B-309.4
Provide note on faucets: “Hand-operated controls for faucets shall be located within accessible reach ranges.” §11B-308.1
Exposed pipes and surfaces
Provide note on exposed pipes and surfaces:” Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact.” Water supply includes hot-water pipe and cold-water pipe. §11B-606.5
Provide note on exposed pipes and surfaces:” There shall be no sharp or abrasive surfaces under lavatories.” §11B-606.5
MIRRORS
Provide dimension line on mirror located above lavatory with the bottom edge of reflective surface 40 inchesmaximum above the finished floor. The maximum dimension implies construction tolerance is not permitted. §11B-603.3
Provide dimension line on mirror not located above lavatory with the bottom edge of reflective surface 35 inchesmaximum above the finished floor. The maximum dimension implies construction tolerance is not permitted. §11B-603.3