HomeMy WebLinkAbout262967_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101103046 PROJECT ADDRESS: 1710 W Eleventh St PLAN CHECK ENGINEER: Lee, WayneTEL:714 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/5/2020 INITIAL REVIEW 3/19/2020 EXPIRATION 8/3/2020 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Quoc Do 3. TEL: (714)458-5374 FAX: VALUATION: $20,000.00 EMAIL: doquocpl@yahoo.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plan resubmitted without the red markup set may result in delayed review time and additional plan check fee. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Public Works Agency approval (647-5039). Sheet A-001. In the scope of work, item #3 and #4 are cross-out by ink. If these are not part of the scope, please complete delete them from plan. In addition, remove the concrete work on the site plan and remove them from permit application form. Sheet A-001. Indicate flood zone type is type “X”. Sheet A-001. Indicate whether building is equipped with automatic fire-sprinkler system. Sheet A-001. Add 2019 California Energy Code to the applicable codes. Sheet A-101. Under utility symbols, the lighting note #B, change “or” to “and” at the following sentence: “… shall be high efficacy or and shall be controlled by a photocontrol/motion sensor…” (2019 CEC 150.0(k)3A). Sheet S-1. Detail 13. Note #7. No soils report is provided in this project. Revise dowel spacing to 18” o.c. maximum in accordance with city’s policy.