Loading...
HomeMy WebLinkAbout263887_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101103369 PROJECT ADDRESS: 2662 S Grand Ave PLAN CHECK ENGINEER: Lee, WayneTEL:714 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 3/4/2020 INITIAL REVIEW 3/30/2020 EXPIRATION 8/31/2020 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Randall Jepson 3. TEL: (714)288-8700 FAX: (714)272-9000 VALUATION: $5,000.00 EMAIL: randy@pjparch.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Sheet A1.1. Under “site and building data”, instead of S occupancy, show the assigned occupancy to either S1 or S2 in accordance with 2019 CBC Chapter 3.Sheet A1.1. Please print the site plan to match the scale specified.Sheet A1.1. Show an accessible path of travel from an accessible parking space to the accessible exterior entrance of unit 2662. (exterior accessible P.O,T. is required from both public street and accessible parking to accessible building entrance)Sheet A1.1. As part of the demolition permit, the owner spends at least 20% of the valuation of improvements on priority items listed under 2019 CBC 11B-202.4 exception 8. Please show:Adjusted construction cost on the first sheet for this interior demolition project.Items to be upgraded to 2019 code with costs, justify spending at least 20% of the adjusted construction coston the existing, not-compliant items.Per item b, provide relevant accessibility details.Sheet A1.1. Revise detail 1 to provide diagonal accessible parking space detail on plan in complying with CBC 11B-502 also refer to Fig. 11B-502.2, Fig 11B-502.3 and Fig 11B-502.3.3. Please verify on plan the parking space meets the minimum dimensions.Add the following note to plan: “Building/suite/unit shall not be occupied until a permit for tenant improvement is issued and finaled”Sheet A2.1. Provide wall legend to identify the existing walls to remain and the non-load bearing partitions to be removed.