Loading...
HomeMy WebLinkAbout262245_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101102835 PROJECT ADDRESS: 1231 E Dyer Rd Unit# 200 PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862 EMAIL: fHeidari@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): A-2, B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 1/14/2020 INITIAL REVIEW 1/27/2020 EXPIRATION 7/12/2020 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Sheila Andelin 3. TEL: (949)757-6996 FAX: (949)757-6999 VALUATION: $1,044,000.00 EMAIL: o3design@aol.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.Please verify the tenant improvement area for this space. My calculation shows over 29,000 SF. Please verify this. The building permit application calls for 19,000 SF of TI area.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceSubmit a signed copy of the contract showing labor and materials for all work to be done under the subject building permit application. The plan check engineer may accept the contract price as the valuation of improvements for unique/unusual projects in lieu of using a cost per square foot basis.The valuation of improvements for the subject building permit application has been calculated to be $ 1,044,000.00.Show on the plans: - Occupancy Classification(s)Ramps with a rise greater than 6” shall have handrails on both sides. Detail 16/D2 does not show this.CBC Section 1008.2.1, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Please make a note on the drawings.The accessible route of travel shall be the most practical direct route between accessible building entrances, accessible site facilities, and the accessible entrance to the site. Please see the red marks on sheet HC1 for locating the accessible route out of the vehicles way.Sanitary facilities serving the area of new work shall be disabled accessible. Revise the drawings to show compliance with CBC Section11B-213.3.1. When 6 or more toilet compartments are provided or when combination of toilet compartments and urinals are 6 or more.Provide structural calculation and construction details for proposed +12” raised floor in the room near the break room.