Loading...
HomeMy WebLinkAbout263177_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 103103108 PROJECT ADDRESS: 2724 S Susan St PLAN CHECK ENGINEER: Lee, WayneTEL:714 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/12/2020 INITIAL REVIEW 3/26/2020 EXPIRATION 8/10/2020 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Lisa Risner 3. TEL: (626)812-9722 FAX: VALUATION: $9,600.00 EMAIL: Permits@qmhinc.com FLOOD ZONE: X-0602320258J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Please return marked up set of drawings with corrections.Please update governing codes to 2019 version on all sheets.Please indicate if building is equipped with fire-sprinkler.Sheet 2. Please show the following information on plan: (see red marks on plan)Common path of travel path and distance. Per CBC Table 1006.2.1, maximum distance is 100 feet for S occupancy.Exit access travel path and distance. Per CBC Table 1017.2, maximum distance is 200 feet for S-1 occupancy without fire sprinkler system.Because of maximum common path of travel is limited to 100 feet, two exits are required in the warehouse area (occupancy S1), provide and show two exits on the plan.