HomeMy WebLinkAbout265106_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101103668
PROJECT ADDRESS:
400 N Tustin Ave Unit# 240
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
II A
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/28/2020
INITIAL REVIEW
7/2/2020
EXPIRATION
11/24/2020
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Bert Elliot
3.
TEL:
(714)840-5488
FAX:
VALUATION: $253,274.00
EMAIL:
elliottarc@socal.rr.com
FLOOD ZONE: X-0602320277J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
General / Instruction Comment
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Please return marked up set of drawings with corrections, if it was picked up.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet G-001:Project address: Please include suite 225 for the relocation of the demising wall. Accessible elevators: Please provide details for accessible elevator to show compliance with 11B-407. Sheet G-401:Detail C1, Accessible Parking Plan:Truncated dome shall not locate/encroach into vehicular area, such as parking area, driveway, access aisle, etc. Please remove and relocate existing truncated dome where it was misplaced. Accessible parking shall arrange so that people use it do not require to travel behind a vehicle. Please coordinate and revise plan accordingly. Sheet A-100:Please provide wall legend for the new demising wall between suite 240 and suite 225. Please revise code referenced under the Building Plan Legend to reflect with 2019 code edition. Sheet A-101:Please provide egress plan for the suite 225 with occupant load calculation and means and egress. On the plan, please show/provide tactile exit sign where occurred/required. General Floor Plan Notes and Legend notes – Please revise notes to reflect with 2019 code edition. Infilled fire-rated wall at existing opening: Please provide wall detail and clearly cross-reference detail onto the plan. Sheet A-102:Please review and revise notes to reflect with the 2019 code edition.