HomeMy WebLinkAbout265865_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101103877
PROJECT ADDRESS:
2510 S Bristol St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/23/2020
INITIAL REVIEW
7/6/2020
EXPIRATION
12/20/2020
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Ken Fang
3.
TEL:
(909)569-2069
FAX:
VALUATION: $80,000.00
EMAIL:
CND9@me.com
FLOOD ZONE: X-0602320259J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
General / Instruction Comments
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Please note on plan: This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet T-1:Accessible path of travel: Please note on plan – accessible path of travel shall be 5% maximum slope, measured in the direction of travel, and 2% cross-slope. Sheet A-1:For clarity, please show dimensions for interior walls so that wall and openings can easily located. Hallway leading to the accessible restroom: Please show/provide minimum clear of 44” between the wall and column. Please show/provide additional exit sign at hallway leading to the exit door(s). Please show/provide minimum 36” clear at least on one side of the equipment (chair / table). At the open foot message area – Please show/provide wheelchair space at the message chair.