HomeMy WebLinkAbout264824_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101103612 PROJECT ADDRESS: 1710 E Seventeenth St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/13/2020 INITIAL REVIEW 5/26/2020 EXPIRATION 11/9/2020 RECHECKS: 1.7/21/2020 PROJECT APPLICANT CONTACT PERSON: 2. Danny Kim 3. TEL: (213)388-6642 FAX: VALUATION: $150,000.00 EMAIL: dkim@dgbamerica.com FLOOD ZONE: X-0602320164J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS General Comments / Instruction All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.Plan check fee is underestimated. Additional plan check fee is required. Sheet S-4: New 8x12 header and its supported columns: Please provide details to show how the new 8x12 beam and its support are supported for out-of-plane loads. 2nd Review Comment: Response was incomplete. It’s still unclear how the 8x12 beam is supported for out-of-plane. Structural CalculationExisting freestanding structures supporting new solid metal siding – Please provide wind analysis to justify the existing freestanding structures are sufficient to support the new solid screening/siding. State all assumptions. Please use wind design provision under the ASCE7-16 Standard. 2nd Review Comment: Could not locate information for the existing freestanding structures. Please review existing structures for added solid metal siding – check members and footing. State all assumption.