Loading...
HomeMy WebLinkAbout266989_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101104173 PROJECT ADDRESS: 1308 W Seventh St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/30/2020 INITIAL REVIEW 8/13/2020 EXPIRATION 1/26/2021 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Leticia Portocarrero 3. TEL: (714)721-3412 FAX: VALUATION: $150,000.00 EMAIL: lettyp67@yahoo.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.General Comments & ApprovalsAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). -Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. -Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). Sheet 1: On the plan, please specify Occupancy Groups (R-3 / U). Site plan: Please show surface drain slope and pattern. Lot shall be graded to drain surface water away from foundation walls. The grade shall fall a minimum of 6” within the first 10’ (5%). Please revise site plan accordingly. Sheet 2 & 3: General notes at the top right corner of the sheet – please revise notes to specify 2019 Code edition. Plumbing notes: Please revise flow rate for the water closet to reflect with the 2019 California Green Building Code. Detail 1/6 called out for the column protection was not applicable. Please revise detail to show protection for the wood post. Energy Conservation and Title 24 Calculation Please provide updated Title 24 calculation and Compliance forms for the 2019 California Energy Code. Photovoltaic system(s) is/are required for all newly constructed residential building. On plan, please show compliance with Section 150.1 (b) or 150.1 (c). On the plan, please specify minimum size of PV system will be installed (verify with Title 24 calculation). Structural Review Comment: Please provide two hard copies of the soil report with engineer stamp and signature for final review and approval. Sheet 5, Foundation: Please provide/show continuous footing at wall line between bedroom 2 and stairway. Sheet 6, Roof Framing Plan: Please show bearing location of hip beam 3.