PLAN CHECK NO:
101104260
PROJECT ADDRESS:
1905 1/2 W Hall Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/6/2020
INITIAL REVIEW
8/27/2020
EXPIRATION
2/2/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Jeff Zanjani
3.
TEL:
(714)240-5136
FAX:
VALUATION: $45,000.00
EMAIL:
jeffzanjani99@gmail.com
FLOOD ZONE: X-0602320259J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.General & ApprovalAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
Sheet 1:
There were two sheet 1 – Please remove one sheet.
Please revise job address to the ½ address (1905-1/2 W. Hall Ave) for the proposed ADU. Job address shall be provided on all plan sheets including structural plans.
Scope of work: Please include the laundry addition to the main house. Two permit applications (plan check numbers) are required.
Sheet 2a:
Water heater shall be accessible to both residences (units). Please relocate water heater or provide additional water heater for the main house.
New laundry room: Please clarify whether it’s accessible from both units.
Please specify fire-rated door, self-closing and air-tight for door at fire-rated wall between two residences.
Please provide detail for the one-hour fire-rated wall. Wall shall extend from foundation/slab to the roof sheathing.
There were two sheets 2a – Please remove duplicated plan.
On the plan, please show heating source for the proposed ADU.
Title 24 Energy Conservation:
Please provide Title 24 calculation and Compliance forms.
Provide building sections to show building envelope (wall and ceiling insulation).
Structural Comments:
Due to conversion of an un-habitable space (garage) to a habitable space, reinforcement of lateral resisting walls are required. Please provide braced/shear walls at the perimeter of the existing garage conversion.
Provide detail of the new infilled wall at the existing garage opening. Show attachment at top and bottom – Concrete curb is required at the sill plate.
Please show/provide existing roof framing and ceiling framings. Provide additional ceiling joists for new ceiling drywall. Provide details. Details shall be clearly cross-reference onto the plan.
Details provided on sheet D-1 shall be clearly cross-referenced onto the plan. Delete/omit detail that does not apply to the project.
Plan shall be stamped, signed, and dated by the engineer of record. Electronic stamp is acceptable; however, photocopied or reproduced plans are not acceptable.