HomeMy WebLinkAbout264622_3_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101103547
PROJECT ADDRESS:
2331 N Olive Ln
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/11/2020
INITIAL REVIEW
5/19/2020
EXPIRATION
11/7/2020
RECHECKS:
1.7/27/20
PROJECT APPLICANT CONTACT PERSON:
2.
Randy Orozco
3.
TEL:
(714)504-6470
FAX:
VALUATION: $60,000.00
EMAIL:
randy@rpodesigns.com
FLOOD ZONE: X-0602320144J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.
General / InstructionAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit three corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Public Works Agency approval (647-5039).
Sheet S4:
Provide detail to show transfer of lateral loads from roof diaphragm to lateral resisting system blow. Details shall be clearly cross-reference onto the plan.
2nd Review Comment: Gable end roof patio – Please provide detail to show transfer of latera loads from roof diaphragm to the steel columns. Glazing are proposed at the gable – shear transfer through those glazing area is insufficient. Please coordinate and revise plan accordingly.
Structural Design
Structural calculations were not provided. Please provide structural calculation for the proposed patio. Provide vertical and lateral analysis.
2nd Review Comment: Seismic analysis – Please revise calculation to use R = 1.25 for cantilever columns.
Plan review will continue at time of resubmittal.