HomeMy WebLinkAbout268929_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101104846
PROJECT ADDRESS:
2510 N Valencia St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/5/2020
INITIAL REVIEW
11/10/2020
EXPIRATION
4/3/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Michael Williams
3.
TEL:
(714)366-9020
FAX:
(714)288-8833
VALUATION: $47,000.00
EMAIL:
crossdesignandconstruction@gmail.com
FLOOD ZONE: X-0602320163J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
Sheet TI:
On the plan, please provide the applicable codes – 2019 of California Residential Code, Building Code, Mechanical Code, Electrical Code, Plumbing Code, Energy Code and Green Building Code.
New steps leading to the existing pool: Please show/provide pool safety barrier.
Sheet A1.0 through A2.3:
Standing seam roof: On the plan, please provide/specify ICC / UL listing report number.
Stairways/steps:
On the plan, please provide information for the stairways/steps. Show run (11” minimum) and rise (7.75” maximum) dimensions.
Stairway with 4 or more risers shall be provided with handrails. Provide handrails not less than 34" or more than 38" above the nosing of tread. (R311.7.8.1)
Guardrails: Please revise guardrails to show 42” minimum height.
Provide construction detail for the stairways. Clearly cross-reference details onto the plan.
Provide structural detail for the guardrails. Guardrails shall design to withstand a 200-lb force apply horizontally at top of guardrails.