Loading...
HomeMy WebLinkAbout269935_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105138 PROJECT ADDRESS: 3350 S Bristol St Unit# B PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830 EMAIL: aso@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/4/2020 INITIAL REVIEW 11/19/2020 EXPIRATION 5/3/2021 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Vicky Li 3. TEL: (714)906-5714 FAX: (888)473-9995 VALUATION: $20,000.00 EMAIL: vickyli8875@yahoo.com FLOOD ZONE: X-0602320259J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Please return marked up set of drawings with corrections.Sheet T-1Revise the project address to 3350 S. Bristol St., Suite B,Santa Ana, CA 92704.Under Code Information, the plan shows the building does not have a fire sprinkler. However, according to City record, this is a sprinklered building. Verify if a sprinkler system is installed in this building.Revise the sheet number and titles on drawing index. The plumbing sheets and electrical sheets are not included in this plan set.Sheet A-3A bench is shown in the waiting area. Provide accessible requirements per CBC Section 11B-903 on the plan.Correct the cross-referenced-detail number on the restroom.The plumbing fixture locations does not match detail 2/D-2. Correct the floor plan or revise all the elevation drawings on sheet D-2 as necessary.