HomeMy WebLinkAbout266456_4_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101104021
PROJECT ADDRESS:
2844 S Croddy Way
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B, F-1, S-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
7/9/2020
INITIAL REVIEW
7/27/2020
EXPIRATION
1/5/2021
RECHECKS:
1.9/29/20
PROJECT APPLICANT CONTACT PERSON:
2.10/14/20
Sami Pakbaz
3.
TEL:
(626)727-8900
FAX:
VALUATION: $600,000.00
EMAIL:
spakbaz@infrastructurearchitects.com
FLOOD ZONE: X-0602320258J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.Reminder: The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet A2-0 & A3-0:Wall Types referenced to sheet A8.1 for wall type and detail, but sheet A8.1 was not provided. 2nd Review Comment: Pre-fab insulated wall and ceiling panel – On the plan, please provide prefab wall and ceiling panel specification including manufacturer’s name, listing number, panel span table, construction details, etc. 3rd Review Comment: Wall and ceiling panel information as required above shall be provided prior to building plan check approval. They cannot be as a deferred item.