PLAN CHECK NO:
101105229
PROJECT ADDRESS:
2329 1/2 N Santiago St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/17/2020
INITIAL REVIEW
12/3/2020
EXPIRATION
5/16/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Chris Salas
3.
TEL:
(818)426-3891
FAX:
VALUATION: $35,000.00
EMAIL:
csalas96@aol.com
FLOOD ZONE: X-0602320163J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
Sheet A2 & A3: Existing building
Please note on plan “FOR REFERENCE ONLY”
Sheet A4:
On the plan, please show/provide door landing at both exterior doors. Landing shall be minimum 3-ft measured in the direction of travel, and width equal to door opening.
Please specify tempered glass for glazing in door and within of 24” of door.
Detail 4/A4, one-hour fire-rated wall: Please revise detail show the 5/8” type ‘X’ gypsum board extending to the underside of the roof sheathing.
Sheet A5:
North Elevation: Stucco wall is required for the one-hour fire-rated wall. Please clarify.
Structural Comments:
Concrete curb is required at existing garage door to be infilled. Please coordinate and revise foundation wall detail at infilled wall.
Detail 11 & 12/S1: please coordinate with fire-rated wall. Additional blocking is required for drywall extending to the underside of roof sheathing.
Final plan shall be stamped, signed and dated by the engineer of record.