HomeMy WebLinkAbout270208_2_Corrections.docx
PLAN CHECK NO:
103105232
PROJECT ADDRESS:
2001 E First St Unit# 209
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830
EMAIL:
aso@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/17/2020
INITIAL REVIEW
11/20/2020
EXPIRATION
5/16/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Jeff Beddow
3.
TEL:
(949)722-7400
FAX:
(949)722-8855
VALUATION: $18,000.00
EMAIL:
jeff.saproperties@gmail.com
FLOOD ZONE: X-0602320277J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Please return marked up set of drawings with corrections.Sheet T1.0Under Building Data, the occupancy use is shown as outpatient clinic. Submit a letter describing in detail the use of proposed outpatient clinic based on chapter 3 occupancy description of CBC for B or I-2,1 occupancy. Please clarify if building is used for outpatient surgery procedure, include a statement whether or not there will be non-ambulatory patients or medical care that may render ambulatory patients incapable of unassisted self-preservation and the number of each type of patient. Does this business consider as a OSHPD 3 clinic? For OSHPD 3 clinic, the license holder for the proposed OSHPD 3 clinic shall write a letter addressed to the Building Official describing the services to be offered and if the facility is subject to CBC Section 1226. Include a statement whether or not there will be non-ambulatory patients or medical care that may render ambulatory patients incapable of unassisted self-preservation and the number of each type of patient. Clarify use of proposed medical building as I-2.1 or limited to B occupancy only.Reference 2019 edition of California Building Code (CBC) under General Note #4.Delete General Note #12.Egress Table shows the combines area of 2,614 square foot. However, Building Data shows 2,823 square foot. Fix discrepancy.Specify the Egress Table on the second floor is for unit 209 only.On the Egress Table, use factor of 0.2 for calculations. This building does not have a sprinkler in order to use the 0.15 factor.On the Egress Table, the width provided is shown as 66 inches. Show this width dimension of the floor plan.On the site plan, show a continuous Path of Travel from the N. Golden Circle Drive to the entrance door of unit 209.Sheet A1.0Specify the occupancy group and use in unit 160. The fire rating of the floor-ceiling assembly is determined by CBC Table 508.4.Show the continuous travel distance from unit 209 to the exit door on the first floor.Sheet A1.1Specify the occupancy group and use in unit 205 and 299.The common path of travel distances are shown incorrectly. See Red Mark A1.1 for reference.Sheet A2Specify egress door size in waiting room and front-office room.Specify door hardware at the egress doors between waiting room and bull-pen area. This door must not have lock for egress purpose.Legend shows new window. Specify size of the window.Correct the reference detail number on the fire extinguisher legend.Reference knee and toe clearance detail 14, 15 on sheet A-3 at Keynote #1.Red Marks – Sheet T1.0Red Marks – Sheet A1.0Red Marks – Sheet A1.1Red Marks – Sheet A-2