HomeMy WebLinkAbout265394_6_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101103755 PROJECT ADDRESS: 2020 S Hathaway St Unit# B PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/11/2020 INITIAL REVIEW 6/25/2020 EXPIRATION 12/8/2020 RECHECKS: 1.8/19/2020 PROJECT APPLICANT CONTACT PERSON: 2.10/5/2020 Jonathan Zane 3.11/9/2020 4. 11/25/2020 TEL: (909)376-7138 FAX: VALUATION: $100,000.00 EMAIL: jlzane@adelphia.net FLOOD ZONE: X-0602320276J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Please return marked up set of drawings with corrections, it was picked up. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process.Police Department approval on the corrected/final set of drawings (647-5840)Public Works Agency approval (647-5039) Orange County Fire Authority (714) 573-6100Sheet A-2.1:Please provide a Wall Legend to show existing vs. new construction. 3rd Review Comment: Type III-B construction – The exterior wall shall be constructed with a noncombustible material complying with Chapter 6, CBC. Please revise plan accordingly. 4th Review Comment: Infilled wall – Exterior wall shall be noncombustible construction. Please coordinate and revise plan accordingly. 5th Review Comment: Plan has not been revised. Noncombustible construction is required for type III-B construction. Please clarify what is the small room in the VEG Room 1 (adjacent to the stairway). 3rd Review Comment: No response provided. Please specify/label the room/space at corner of stairway and Veg room 1. 4th Review Comment: Please comply. 5th Review Comment: Please clearly specify Mechanical Shaft on the plan. Please provide floor plan for the existing mezzanine. 3rd Review Comment: Please show/provide floor plan for the existing mezzanine and second floor for reference. Note –mezzanine plan and second floor plan were provided on the initial submittal. Fire-rated corridor and passage way: on the plan, please clearly identify fire-rated walls and provide construction details for the fire-rated assembly. Details shall be clearly cross-reference onto the plan. 3rd Review Comment: Response was incomplete. 4th Review Comment: Response was incomplete. Please comply with the comments below.Please clearly show fire-rated wall – Use different wall legend for fire-rated wall so that it can be easily identified. Please provide detail to show fire-rated wall assembly extended from slab to roof sheathing. 5th Review Comment: Plan was not revised. Please comply with the comments above. Referenced detail 1/A-3.3 – Please revise detail to show full one-hour wall assembly. Referenced to garage and living space were insufficient. Structural:3rd Review Comment: Structural calculation and details were not provided. Comments below are remained applicable. Please provide structural calculation and details for the new opening at the existing exterior concrete wall. 4th Review Comment: Please provide structural calculation and details for the wall opening. Check existing wall for in-plane shear and out-of-plane loads. 5th Review Comment: No response provided nor structural calculation and details were provided. Please comply with the comments above. Please provide roof plan and framing information to show location of new roof top units and its support. Structural calculations are provided with the submittal package. Please clarify whether the structural improvements are part of this permit application or they are provided for reference only. PLEASE NOTE: PLAN CHECK COMMENTS WERE NOT ADDRESSED. ADDITIONAL PLAN CHECK FEES WILL BE REQUIRED AFTER THIRD SUBMITTAL AND THEREAFTER.