HomeMy WebLinkAbout268704_3_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101104756 PROJECT ADDRESS: 928 W Fairbrook Ln PLAN CHECK ENGINEER: Lee, WayneTEL:714 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 9/25/2020 INITIAL REVIEW 10/4/2020 EXPIRATION 3/24/2021 RECHECKS: 1.11/18/2020 PROJECT APPLICANT CONTACT PERSON: 2. John Lane 3. TEL: (714)795-1921 FAX: VALUATION: $60,000.00 EMAIL: John@depinnoroofing.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a). This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Public Works Agency approval (647-5039). PLAN CHECK COMMENTS: Sheet A-1 through A-6. All persons preparing plans for others shall sign the architectural plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a). Sheet T24.2. The responsible designer shall complete the page 10 of the CF1R form on the drawing. The signature, date and license number (if applicable) are not available. Sheet A-6. Revise section B-B to indicate that a landing at the rear porch. The elevation of landing shall not exceed 1 ½ inch difference than the threshold of the doorway (7 3/4 inch if door does not swing over the landing or steps) in each direction. (CRC R311.3.1) Sheet A-2 and S-1. Provide construction details on plan for the new raised porch. Please clarify and coordinate with structural engineer and the foundation plan. END OF COMMENTS