HomeMy WebLinkAbout270915_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105462 PROJECT ADDRESS: 515 E Dyer Rd PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): B, S-1, S-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/15/2020 INITIAL REVIEW 1/2/2021 EXPIRATION 6/13/2021 RECHECKS: 1.1/24/2021 PROJECT APPLICANT CONTACT PERSON: 2. Julie Armstrong 3. TEL: (541)389-9659 FAX: VALUATION: $260,165.00 EMAIL: jarmstrong@eeimt.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Public Works Agency approval (647-5039)Sheet T:To be consistence with addressing in our permit record, please omit/remove all the building A,B,C designation. Per City record, there is only one address (one building). 2nd Review Comment: Warehouse Site Plan – Please omit building designation (A, B & C) for consistency. Sheet SH-01:Please clarify information showed as proposed overhead doors, proposed doors, proposed TDR entrance, proposed removed dock cart, proposed demising wall, etc. Please omit information if they are not part of this permit application. 2nd Review Comment: Plan still showed “Proposed overhead” doors and entrances – Please omit proposed openings if they are not part of this permit application. Please coordinate with sheet 001 as well. Sheet 001: Please coordinate and omit information that are not part of this permit application (ex. Door openigs). Sheet 002: Platform and stairwayOn the plan, please clearly specify all member sizes, including columns sizes, beams, stringers, braces, etc. Clearly cross-reference details onto the plan. 2nd Review Comment: Plan must be legible. Please specify and coordinate all part number and member schedule. Plans shall be legible. Please increase font size