HomeMy WebLinkAbout270579_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105357
PROJECT ADDRESS:
2415 1/2 N Forest Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/3/2020
INITIAL REVIEW
1/7/2021
EXPIRATION
6/1/2021
RECHECKS:
1.2/1/2021
PROJECT APPLICANT CONTACT PERSON:
2.
Jason Brooks
3.
TEL:
(714)618-2656
FAX:
VALUATION: $35,000.00
EMAIL:
jacebrooks@gmail.com
FLOOD ZONE: X-0602320144J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
- School District Compliance Certificate; and a copy of the Building Permit School Fee Worksheet, completed by the applicant and city staff, shall be required by the School District to verify the scope of the work.
Sheet A-1:
Exterior wall line 1: Wall located less than 5-ft from the property line shall be constructed with a one-hour fire-rated wall. Please show one-hour wall and provide construction detail for the one-hour fire-rated wall assembly.
2nd Review Comment: Response was incomplete. Please provide minimum 5/8” type ‘X’ on the interior side of wall. Please revise plan and detail 7/D1 to show one-hour wall assembly and extended to the roof sheathing.