HomeMy WebLinkAbout271786_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105716
PROJECT ADDRESS:
2600 S Harbor Blvd
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B, F-1, S-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/25/2021
INITIAL REVIEW
2/7/2021
EXPIRATION
7/24/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Chris Hansen
3.
TEL:
(714)573-0073
FAX:
VALUATION: $75,000.00
EMAIL:
hchansen@msn.com
FLOOD ZONE: X-0602320258J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTSThe applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Please apply building permit for structural repair in 2602 S Harbor Blvd., Santa Ana. This shall be done prior to next recheck. When plans are revised and ready to resubmit back to Buidling Division, please contact Evelyn LaRocca at 714-647-5856 orELaRocca@santa-ana.orgfor an appointment to fill up permit application and submit revised plans for review.Per item #2, revise the project address to 2600 and 2602 S Harbor Blvd. on all sheets and structural calculationif two permits are on the same drawings.Sheet 1. Revise scope of work to add concrete slab alteration in unit 2600 S Harbor Blvd.Sheet 1. Revise scope of work to add storefront alteration in unit 2600 S Harbor Blvd. Submit storefront design or add note to plan if it is deferred submittal.Sheet 5. Show occupancy group in unit 2602 S Harbor Blvd.Sheet 5. Indicate __ hours fire-rating barrier between unit 2600 and 2602 S Harbor Blvd. complying with CBC Chapter 5 or Table 508.4. Currently, plan shows non-rated fire barrier.Sheet 5. Provide dimensions for new partition walls in the restroom and office.Sheet 5. Label all spaces/rooms with occupancy assigned.Provide energy analysis for new storefront compliance with 2019 California Energy Code. Indicate SHGC and U-factor for the storefront.