Loading...
HomeMy WebLinkAbout270915_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105462 PROJECT ADDRESS: 515 E Dyer Rd PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): B, S-1, S-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/15/2020 INITIAL REVIEW 1/2/2021 EXPIRATION 6/13/2021 RECHECKS: 1.1/24/2021 PROJECT APPLICANT CONTACT PERSON: 2. Julie Armstrong 3. TEL: (541)389-9659 FAX: VALUATION: $260,165.00 EMAIL: jarmstrong@eeimt.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Public Works Agency approval (647-5039)Sheet SH-01:Please clarify information showed as proposed overhead doors, proposed doors, proposed TDR entrance, proposed removed dock cart, proposed demising wall, etc. Please omit information if they are not part of this permit application. 2nd Review Comment: Plan still showed “Proposed overhead” doors and entrances – Please omit proposed openings if they are not part of this permit application. Please coordinate with sheet 001 as well. 3rd Review Comment: Sheet SH-01 – Information on sheet SH-01 was turned off. It was just a blank sheet; please provide sheet SH-01 with applicable information. Reminder: Please clearly cross-reference to applicable details for proposed storage racks and crossover platforms so that it would be clearly reflect the scope of work. General: Prior to resubmitting plans to Building Safety for review, the applicant should review the plans sets for complete and legible. Additional plan check fee will be required after the third (3rd) plan review and thereafter.