HomeMy WebLinkAbout272032_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105784
PROJECT ADDRESS:
2721 S Hotel Terrace Dr
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830
EMAIL:
aso@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V A, SPK
OCCUPANCY CLASSIFICATION(S):
R-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
2/1/2021
INITIAL REVIEW
2/27/2021
EXPIRATION
7/31/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Alex Rojas
3.
TEL:
(469)662-8239
FAX:
VALUATION: $138,824.00
EMAIL:
alexrojas@adcook-grp.com
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.
Sheet A0.1
Please provide Architect On Record’s signature on the architect seal on every sheet.
Revise the governing code to 2019 California Building Code under the Applicable Codes section. City of Santa Ana does not enforce the 2010 ADA standards on commercial buildings.
Provide the following building information: construction type, occupancy group, and the type of sprinkler system.
Provide a detailed description for the scope of work on this project.
Sheet A1.0
Detail 1: Specify the marking requirements per CBC Section 11B-503.3.3.
Detail 1: Specify maximum slope on the passenger drop-off zone.
Detail 5: Cross-reference detail 5/A1.0 on the site plan.
Detail 5: Specify the actual type of hardware on the doors.
Detail 6: Cross-reference detail 6/A1.0 on the site plan.
Detail 6: Show a clear-floor space in front of the new lavatory.
Detail 6: Reference detail 10/A2.0 for the new lavatory.
Detail 6: Specify the lavatory height.
Detail 6: Specify a minimum of 18 inches from the centerline of lavatory to the adjacent wall.
Detail 6: Show a turning space of 60 inches diameter minimum in the men and women’s’ restrooms.